11. Check whether there is a burner pressure regulator (1) attached to the gas
control, or simply a blank plate (5).
Note
If the supply pressure for a gas category is the same as the burner pressure
(see the gas data table (3.4.3 "Gas data")) then the gas control must be fitted
with a blank plate with cork gasket. A burner pressure that deviates in
comparison to the supply pressure requires the use of a burner pressure
regulator with rubber gasket. Each conversion kit contains all the necessary
components.
12. If the blank plate or burner pressure regulator need to be replaced:
-
Unscrew the connector (4) of the gas control.
-
If necessary, remove the blank plate or burner pressure regulator (5)
or burner pressure regulator (1).
-
If necessary, fit the blank plate or burner pressure regulator supplied
with the conversion kit.
-
Fit the connector (4) of the gas control.
13. Check the supply pressure and burner pressure (3.11 "Checking the supply
pressure and burner pressure").
14. Remove the sticker showing the new gas category from the conversion kit,
and attach it below the appliance's rating plate. This clearly indicates that the
appliance may no longer be run on the gas for which it was originally
supplied.
15. Start the appliance (9.1 "Starting and running").
Содержание ADMR - 40
Страница 4: ...4 Instruction manual ADMR gis ...
Страница 10: ...Introduction 10 Instruction manual ADMR 1 gis ...
Страница 54: ...Shutting down 54 Instruction manual ADMR 10 gis ...
Страница 62: ...Main menu 62 Instruction manual ADMR 11 gis ...
Страница 76: ...is Instruction manual ADMR 76 ...
Страница 78: ...Maintenance frequency 78 Instruction manual ADMR 14 is ...
Страница 84: ...Performing maintenance 84 Instruction manual ADMR 15 s ...
Страница 92: ...Appendices 92 Instruction manual ADMR 17 is ...
Страница 94: ...Instruction manual ADMR 94 ...