110 Indoor / 110 Outdoor Service Manual
Ver. 1.01
51
CONFIDENTIAL
12-7. (A) ON/OFF conditions: Overview
The following table shows the ON/OFF conditions of the water heater.
ON/OFF Conditions
Conditions needed to turn
ON.
The BTU requirement is more than 29,800 BTU/h.
OR
Inlet temperature is lower 5.4°F than the set
temperature and the BTU requirement is more than
14,880 BTU/h
Conditions needed to turn
OFF.
The BTU requirement is lower than 11,900 BTU/h.
OR
*Inlet temperature is higher than the temperature that
is -18°F below the set temperature.
*Only if the set temperature is below 115°F (46
˚
C).