background image

Hacousto Holland bv 
Industrieweg 87 
2651BC  Berkel & Rodenrijs 

 

CONTROLLER user manual 

Author: 

DD 

 

 

 

Page 6 of 14

 

 

 

4.

 

Back panel 

 
 
 

 

 
 
 

 

Analog audio inputs 

In  the  left  section  the  Controller  provides  2  independent  analogue  audio  inputs  dedicated  for  BGM 
broadcast.  
2 x mono, balanced, line level (0dbU / 0.775Vrms), 15kΩ input impedance. 
Connect your auxiliary audio source for background music or low priority external paging microphone here. 
 

 

 

AMP LINK 

The AMP LINK (RED vertical cat5 cable) is the secured bus connecting the Impact 
Controller to up to 16 x DCA2.500 amplifiers. Based on RS485, this internal system 
bus provides: 

-

 

2 balanced audio channels across the entire AMP LINK chain, monitored; 

-

 

Control and diagnostics data interface. 

In order to work properly, the AMP LINK must be set up in the configuration settings 
(“Amplifier” tab). 
Amplifiers connected to the AMP-LINK are addressed and initiated by the Controller 
at each system reboot.  
NOTE: Reboot the system (Controller front panel RESET) after each modification 
applied to any amplifier on the AMP-LINK, including: 

-

 

replacing / adding / removing a DCA2.500 amplifier (along with new configuration settings); 

-

 

changing DIP-switch settings on DCA2.500 back panel; 

-

 

replacing the battery; 

24V DC input 

(parallel connectors) 

Analog audio 

inputs 

AMP LINK 

Local network  

ports 

Global network 

ports 

Ethernet ports 

Device ID  microSD 

card 

USB 

CAL button 

(not used) 

Reset 

button 

GPO 

Relay outputs 

EVAC inputs 

Содержание IMPACT

Страница 1: ...nual of the 4EVAC Controller the head unit of the 4EVAC Impact voice evacuation system REVISION AND APPROVAL Rev Date Nature of Changes Approved By 01 05 06 2019 Original draft DD 02 10 03 2020 Update...

Страница 2: ...TEM FAULT 4 NETWORK FAULT 5 3 Front buttons 5 SILENCE 5 LAMP TEST 5 EVAC 5 ALERT 5 RESET 5 4 Back panel 6 Analog audio inputs 6 AMP LINK 6 Local network 7 Global network 8 Ethernet option 9 Device ID...

Страница 3: ...essages BGM broadcasts microphone consoles I O extensions and cabling infrastructure 1 General information 4EVAC Controller is the head unit of the 19 rack mounted Impact Voice Evacuation System The C...

Страница 4: ...is Impact controller and amplifiers are healthy and another device in the network is reporting fault state POWER SUPPLY FAULT Indicates a power supply fault of the local Impact system where at least o...

Страница 5: ...TEST Press to verify visual LEDs and audible indications buzzer of the front panel of the local Controller and local amplifiers connected to AMP LINK of local Controller EVAC Press to trigger the EVA...

Страница 6: ...lanced audio channels across the entire AMP LINK chain monitored Control and diagnostics data interface In order to work properly the AMP LINK must be set up in the configuration settings Amplifier ta...

Страница 7: ...the configuration and diagnostic software information Amplifier 1 is the first unit on the bus i e the closest and connected directly to the controller Amplifier 2 is the second unit in the chain etc...

Страница 8: ...ms 100m AWG24 8 42ohms 100m AWG22 5 24ohms 100m 1 250m 250m 250m From L NET 180mA 2 186m 250m 250m From L NET 360mA 3 107m 170m 250m Power injector 540mA 4 71m 113m 182m Power injector 720mA 5 53m 85m...

Страница 9: ...ontents When the memory card is removed damaged or its contents are corrupted the Controller will report a system fault During a system fault caused by a memory error it enters a safe state where the...

Страница 10: ...ulse length of the reset signal is configurable from 0 disabled to 5000ms in the configuration settings 4 11 4 USR DEF This relay output is not in use EVAC inputs There are 16 monitored inputs dedicat...

Страница 11: ...ds on length typ N x 0 75 1 5mm2 N number of individual triggering signals from to fire detection system 1000m EVAC FAULT RESET out 3 Potential free relay output n a 1000m GPI 8 Pull down input n a 10...

Страница 12: ...DC supply input 24 30V DC from DCA2 500 Power consumption 140 mA 24V DC Inputs 2 x BGM 2 x balanced analogue audio mono input 0dBu input impedance 15k 16x EVAC in monitored analogue inputs 4 7k 10k E...

Страница 13: ...1434 Max total system output power 119 5 kW Number of simultaneous network audio channels 2 Network audio transmission latency 0 3 ms per device Local network Architecture Master slave up to 16 slave...

Страница 14: ...Berkel Rodenrijs 4EVAC Controller user and installation manual Author DD Page 14 of 14 M A D E I N T H E N E T H E R L A N D S 4EVAC is a trade name of Hacousto Holland bv Industrieweg 87 2651BC Berk...