Hacousto Holland bv 
Industrieweg 87 
2651BC  Berkel & Rodenrijs 

 

CONTROLLER user manual 

Author: 

DD 

 

 

 

Page 13 of 14

 

 

 

All information provided in this document is subject to change without notice. 4EVAC may also make improvements and/or changes 
in the products described in this information at any time without notice. 

 
 

 
 
 

 

 

Mechanical 

 

 

Dimensions (HxWxD) 

4.4 x 44 x 34 cm (1U) 

 

Weight 

4 kg 

 

Housing material 

Steel 

 

IP rating 

IP 30 

 

Mounting 

19” rack mounting 

Operating conditions 

 

 

Temperature (Ambient) 

-5 ~ 40°C 

Max. Temperature (Device) 

65°C 

 

Relative humidity 

max. 90% (non condensing) 

Storage temperature 

-40 ~ 70°C 

 

 

Network system

 

 

Max. number of devices in the network 

254 

Max. number of zones 

254 

Max. number of loudspeaker lines 

1434 

Max. total system output power 

119.5 kW 

Number of simultaneous network audio channels 

Network audio transmission latency 

0.3 ms per device 

Local network 

 

 

Architecture 

Master-slave, up to 16 slave devices per Controller  

 

Connection 

3 x L-Net port, RJ-45, powered daisy chain, digital audio & control data 

 

Cabling 

X-over FTP CAT5e (or higher) 

 

Current consumption 

max. 500 mA per L-Net port 

 

Max. length of local link (node-to-node) 

 

 

 

default 

250 m 

 

 

with twisted-pair extenders 

500 m 

 

 

with MM fiber extenders 

2500 m 

Global network 

 

 

Architecture 

Peer-to-peer, up to 254 Controllers 

 

Connection 

2 x G-Net port, RJ-45, powered redundant ring, digital audio & control data 

 

Cabling 

X-over FTP CAT5e (or higher) / multimode optical fiber 

 

Current consumption 

max. 500 mA per port, reserved only for network extenders 

 

Max. distance between devices 

 

 

 

default 

250 m 

 

 

with twisted-pair extender 

500 m 

 

 

with MM fiber extenders 

2500 m 

Содержание IMPACT

Страница 1: ...nual of the 4EVAC Controller the head unit of the 4EVAC Impact voice evacuation system REVISION AND APPROVAL Rev Date Nature of Changes Approved By 01 05 06 2019 Original draft DD 02 10 03 2020 Update...

Страница 2: ...TEM FAULT 4 NETWORK FAULT 5 3 Front buttons 5 SILENCE 5 LAMP TEST 5 EVAC 5 ALERT 5 RESET 5 4 Back panel 6 Analog audio inputs 6 AMP LINK 6 Local network 7 Global network 8 Ethernet option 9 Device ID...

Страница 3: ...essages BGM broadcasts microphone consoles I O extensions and cabling infrastructure 1 General information 4EVAC Controller is the head unit of the 19 rack mounted Impact Voice Evacuation System The C...

Страница 4: ...is Impact controller and amplifiers are healthy and another device in the network is reporting fault state POWER SUPPLY FAULT Indicates a power supply fault of the local Impact system where at least o...

Страница 5: ...TEST Press to verify visual LEDs and audible indications buzzer of the front panel of the local Controller and local amplifiers connected to AMP LINK of local Controller EVAC Press to trigger the EVA...

Страница 6: ...lanced audio channels across the entire AMP LINK chain monitored Control and diagnostics data interface In order to work properly the AMP LINK must be set up in the configuration settings Amplifier ta...

Страница 7: ...the configuration and diagnostic software information Amplifier 1 is the first unit on the bus i e the closest and connected directly to the controller Amplifier 2 is the second unit in the chain etc...

Страница 8: ...ms 100m AWG24 8 42ohms 100m AWG22 5 24ohms 100m 1 250m 250m 250m From L NET 180mA 2 186m 250m 250m From L NET 360mA 3 107m 170m 250m Power injector 540mA 4 71m 113m 182m Power injector 720mA 5 53m 85m...

Страница 9: ...ontents When the memory card is removed damaged or its contents are corrupted the Controller will report a system fault During a system fault caused by a memory error it enters a safe state where the...

Страница 10: ...ulse length of the reset signal is configurable from 0 disabled to 5000ms in the configuration settings 4 11 4 USR DEF This relay output is not in use EVAC inputs There are 16 monitored inputs dedicat...

Страница 11: ...ds on length typ N x 0 75 1 5mm2 N number of individual triggering signals from to fire detection system 1000m EVAC FAULT RESET out 3 Potential free relay output n a 1000m GPI 8 Pull down input n a 10...

Страница 12: ...DC supply input 24 30V DC from DCA2 500 Power consumption 140 mA 24V DC Inputs 2 x BGM 2 x balanced analogue audio mono input 0dBu input impedance 15k 16x EVAC in monitored analogue inputs 4 7k 10k E...

Страница 13: ...1434 Max total system output power 119 5 kW Number of simultaneous network audio channels 2 Network audio transmission latency 0 3 ms per device Local network Architecture Master slave up to 16 slave...

Страница 14: ...Berkel Rodenrijs 4EVAC Controller user and installation manual Author DD Page 14 of 14 M A D E I N T H E N E T H E R L A N D S 4EVAC is a trade name of Hacousto Holland bv Industrieweg 87 2651BC Berk...

Отзывы: