![background image](http://html2.mh-extra.com/html/4evac/impact/impact_user-manual_3072685011.webp)
Hacousto Holland bv
Industrieweg 87
2651BC Berkel & Rodenrijs
CONTROLLER user manual
Author:
DD
Page 11 of 14
5.
Connections and recommended cable types
How
many
Connector
type
Signal type
Additional
information
Recommended cable
(minimum)
Max. length
Analog audio in
2
pluggable
screw
terminal
block
3.5 mm
Analog
balanced mono
audio, 0dBu
n/a
Balanced shielded
microphone cable, typ. 2
x 0.25mm
2
100m
EVAC in
16
Pull-down input
with fault
detection
(open/short)
EOL resistors 10kΩ
+ 4.7kΩ in series
Depends on length, typ.
N x 0.75~1.5mm2 (N –
number of individual
triggering signals from /
to fire detection system)
1000m
EVAC / FAULT/
RESET out
3
Potential-free
relay output
n/a
1000m
GPI
8
Pull-down input n/a
1000m
GPO
8
Open collector
output
max. 24V
max. 110mA
n/a
Depends on length, typ.
N x 0.75~1.5mm2 (N –
number of individual
triggering signals to
external devices)
1000m
AMP LINK port
1
RJ-45
Line level
analogue audio
+ RS485 data
UTP CAT5e
10m
G-Net port
2
Full duplex RS-
422
Redundant ring
with power
delivery
FTP CAT5e crossover
250m
(between
devices)
Power
limitations
apply
L-Net port
3
Daisy chain with
power delivery
DC Power in
1
Pluggable
screw
terminal
block
5.08mm
24~30V DC
n/a
2 x 1.5mm
2
10m