CONTROLLER user manual
Author:
DD
Page 4 of 14
EVAC
Indicates that the system is in the Voice Alarm state, where at least one zone in the system is occupied by
an emergency audio signal, i.e. a pre-recorded EVAC MESSAGE or LIVE EVAC, when a fireman mic is being
used.
OFF
EVAC status is inactive (quiescent mode)
RED continuous
EVAC status is active
GENERAL FAULT
Indicates that the system is in the FAULT state (general fault indicator), where at least one device in the
system is reporting a fault.
OFF
System is healthy
YELLOW continuous
Local fault is detected
(failure of Impact controller or local AMP LINK amplifiers)
YELLOW blinking
Remote fault is detected
(this Impact controller and amplifiers are healthy and another device in the
network is reporting fault state)
POWER SUPPLY FAULT
Indicates a power supply fault of the local Impact system, where at least one of following faults is reported
OFF
Power supply OK
YELLOW blinking
Battery-related fault:
o
Loss of battery
o
Loss of charger
o
Battery resistance too high
o
Temperature fault
YELLOW continuous
Mains fault
SYSTEM FAULT
Indicates a system fault of the Impact Controller, where:
-
a CPU or program execution is stopped or malfunctioning,
-
there is a corruption of storage memory containing config settings and audio files (SD card).
Where the system fault is caused by a CPU or memory fault, the Controller remains in its “safe state”, where
critical functions (including audio transmission, reaction on control inputs, etc.) are stopped until the fault
is resolved.
OFF
Firmware and settings OK
YELLOW continuous
CPU / program fault