Thank you for choosing 4EVAC as your Voice Evacuation System solution. 
4EVAC Impact is a 19” rack format, EN54-16 certified Voice Evacuation System, dedicated to medium to 
large installations. The Impact system is capable of both standalone and network operation, for a wide 
selection of peripheral devices and remote extensions. 4EVAC Impact is certified in accordance with EN54-
16 and EN54-4, which are harmonized standards under the Construction Products Regulation, mandatory 
in the European Union.  
The 4EVAC Impact system is fully compatible with the Compact 500 Voice Evacuation System. This means 
that  both  systems  can  be  connected  to  one  network,  running  the  same  protocol  in  peer-to-peer 
architecture, operating within the same space of voice evacuation zones, sharing the same audio messages, 
BGM broadcasts, microphone consoles, I/O extensions and cabling infrastructure. 
 
 

1.

 

General information 

4EVAC Controller is the head unit of the 19” rack mounted Impact Voice Evacuation System. The Controller 
covers complete EN54-16 certified functionality, as well as a variety of features essential to Public Address 
applications. 
4EVAC Controller incorporates 16 monitored contact inputs; 8 GPO, 4 relay outputs, 2 analogue audio 
inputs and 2 outputs. In addition, local network interfaces for max. 16 local peripheral devices (e.g. mic 
consoles) and 2 global network ports for interconnecting multiple systems in a redundant ring topology 
are included. 
The Controller is designed to work with 4EVAC DCA2.500 power amplifiers over a 4EVAC proprietary AMP 
LINK protocol. The Controller can also be easily integrated with any third-party PA/VA power amplifier. 

2.

 

Front indicators  

 

 

 
 

 

POWER 

Indicates if the Controller is being powered and if the system is properly booted. 

OFF 

Not powered 

GREEN continuous 

This device is powered and operational. 

GREEN blinking 

This device is booting after power up / reset. 

Содержание IMPACT

Страница 1: ...nual of the 4EVAC Controller the head unit of the 4EVAC Impact voice evacuation system REVISION AND APPROVAL Rev Date Nature of Changes Approved By 01 05 06 2019 Original draft DD 02 10 03 2020 Update...

Страница 2: ...TEM FAULT 4 NETWORK FAULT 5 3 Front buttons 5 SILENCE 5 LAMP TEST 5 EVAC 5 ALERT 5 RESET 5 4 Back panel 6 Analog audio inputs 6 AMP LINK 6 Local network 7 Global network 8 Ethernet option 9 Device ID...

Страница 3: ...essages BGM broadcasts microphone consoles I O extensions and cabling infrastructure 1 General information 4EVAC Controller is the head unit of the 19 rack mounted Impact Voice Evacuation System The C...

Страница 4: ...is Impact controller and amplifiers are healthy and another device in the network is reporting fault state POWER SUPPLY FAULT Indicates a power supply fault of the local Impact system where at least o...

Страница 5: ...TEST Press to verify visual LEDs and audible indications buzzer of the front panel of the local Controller and local amplifiers connected to AMP LINK of local Controller EVAC Press to trigger the EVA...

Страница 6: ...lanced audio channels across the entire AMP LINK chain monitored Control and diagnostics data interface In order to work properly the AMP LINK must be set up in the configuration settings Amplifier ta...

Страница 7: ...the configuration and diagnostic software information Amplifier 1 is the first unit on the bus i e the closest and connected directly to the controller Amplifier 2 is the second unit in the chain etc...

Страница 8: ...ms 100m AWG24 8 42ohms 100m AWG22 5 24ohms 100m 1 250m 250m 250m From L NET 180mA 2 186m 250m 250m From L NET 360mA 3 107m 170m 250m Power injector 540mA 4 71m 113m 182m Power injector 720mA 5 53m 85m...

Страница 9: ...ontents When the memory card is removed damaged or its contents are corrupted the Controller will report a system fault During a system fault caused by a memory error it enters a safe state where the...

Страница 10: ...ulse length of the reset signal is configurable from 0 disabled to 5000ms in the configuration settings 4 11 4 USR DEF This relay output is not in use EVAC inputs There are 16 monitored inputs dedicat...

Страница 11: ...ds on length typ N x 0 75 1 5mm2 N number of individual triggering signals from to fire detection system 1000m EVAC FAULT RESET out 3 Potential free relay output n a 1000m GPI 8 Pull down input n a 10...

Страница 12: ...DC supply input 24 30V DC from DCA2 500 Power consumption 140 mA 24V DC Inputs 2 x BGM 2 x balanced analogue audio mono input 0dBu input impedance 15k 16x EVAC in monitored analogue inputs 4 7k 10k E...

Страница 13: ...1434 Max total system output power 119 5 kW Number of simultaneous network audio channels 2 Network audio transmission latency 0 3 ms per device Local network Architecture Master slave up to 16 slave...

Страница 14: ...Berkel Rodenrijs 4EVAC Controller user and installation manual Author DD Page 14 of 14 M A D E I N T H E N E T H E R L A N D S 4EVAC is a trade name of Hacousto Holland bv Industrieweg 87 2651BC Berk...

Отзывы: