ENGLISH
34
13 "-PRG" MENU FUNCTION OVERVIEW
DISPLAY
ENTRY
DESCRIPTION
STANDARD VALUE
Set value
P03
0 - 100%
Partially open position (percentage of total opening)
25
P10
Direction logic:
rEC
rEc
● The gate opens to the right.
Lin
● The gate opens to the left.
P13.o
0.5" - 1.0'
Warning light pre-warning time in open direction.
AUS
AUS
"Warning light pre-warning time in open direction"
function deactivated.
P13.c
0.5" - 1.0'
Warning light pre-warning time in close direction.
AUS
AUS
"Warning light pre-warning time in close direction"
function deactivated.
P14.o
30 - 100%
Running speed in open direction.
40
P14.c
30 - 100%
Running speed in close direction.
40
P14.S
0 - 70 %
Soft stop speed, max. ≤
P14.o
or
P14.c
20
P16
JA/nEin
Switch off of motor power regulation on start-up (start-up suppression).
nEin
P17.o
0 - 4
Length of warm-up ramp in open direction.
1
0
"Length of warm-up ramp in open direction"
function deactivated.
P17.c
0 - 4
Length of warm-up ramp in close direction.
1
0
"Length of warm-up ramp in close direction"
function deactivated.
P18.o
0 - 100%
Duration of soft stop phase in open direction.
10
0
"Duration of soft stop phase in open direction"
function deactivated.
P18.c
0 - 100%
Length of soft stop phase in close direction.
10
0
"Duration of soft stop phase in close direction"
function deactivated.
P20
Start pulse on gate opening eff ects:
StoP
AUS
● Start pulse is ignored, gate continues to open.
ZU
● Gate stops and closes again immediately.
StoP
● Gate stops.
P21
Start pulse on gate closing eff ects:
StoP
StoP
● Gate stops.
AUF
● Gate stops and opens again immediately.
P22
Start pulse when gate is open eff ects:
ZU
AUS
● Start pulse is ignored, gate remains open.
ZU
● Gate closes again immediately.
PAUS
● Hold-open time is reset.
P23
Start pulse on pedestrian opening eff ects:
StoP
AUS
● Start pulse is ignored, gate continues to open.
ZU
● Gate stops and closes again immediately.
StoP
● Gate stops.
P24
Automatic closing (automatic gate closing):
AUS
AUS
● Automatic gate closing deactivated.
0.5ʺ - 20.0ʹ
● Gate closes after set time.
P25
Quick close function after passage.
AUS
AUS
●
"Quick close function after passage"
function deactivated.
0.5ʺ - 20.0ʹ
● Gate closes after set time.
P25.1
JA/nEin
Quick close function only after passage of both light barriers (type 1 and
type 2). Apply setting in menu P25.
nEin
P27
JA/nEin
Warning light on open gate.
nEin
P28
Function of start inputs (terminal J1/J2/J4):
StAn
nEin
● The control's start inputs are deactivated.
StAn
● Standard mode.
AU.ZU
● Defi ned open and close commands.
totb
● Deadman operation.
dAUF
● Continuous open on continuous signal at start input.
Содержание CX1024
Страница 1: ...www 4ddoors com au instructions for fitting operating and maintenance Sliding operator CX1024 ...
Страница 2: ...2 A B Ø 12 mm Ø 5 5 mm 17 mm 3 mm 2 17 5 mm 3 mm PIC 01 ...
Страница 12: ...ENGLISH 12 DX SX DX SX 11 Figure 11 End positions Max 38 mm 102 mm 12 Figure 12 Distances ...
Страница 37: ...ENGLISH 37 ...
Страница 42: ...2906380 www 4ddoors com au instructions for fitting operating and maintenance Sliding operator CX1024 ...