Specifications
68
Powerware
®
Prestige Series Installation and Operator’s Manual for IBM Applications (3000 VA)
Uncontrolled Copy
Prestige 3000 UPS Technical Specifications
Input Voltage Range
160 to 276 Vac
Input Power Factor
0.95 Typical
Frequency Range
50/60 Hz ±3 Hz
Surge Protection
IEC 801-4
Output Waveform
Sine wave
Output Voltage
(without PPDM)
200/208/220/230/240 Vac ±3%
Online (BTUs)
978
On Battery (BTUs)
1468
Common Mode Noise
Rejection
>60 dB @ 100 kHz
Transverse Mode Noise
Rejection
>80 dB @ 100 kHz
Input Cord
Detachable 2-meter cord
Outlets (UPS Cabinet)
IEC 320 (1)
Output Voltages and Outlets
(with PPDM)
120/208V: 5-15R (2), 6-15R (2), IEC 320-C19 (1)
120/240V: 5-15R (2), 6-15R (2), IEC 320-C19 (1)
220/230/240V: IEC 320-C13 (6), IEC 320-C19 (1)
120/208V: L6-30R (1), 5-15R (4)
120/240V: L6-30R (1), 5-15R (4)
Batteries (10) per cabinet
12 Vdc, 5 Ah, maintenance-free rechargeable lead acid
Battery Cabinet
120 Vdc
Operating Environment
Temperature: 10
C to 40
C
(50
F to 104
F)
Humidity:
5 to 95%
(noncondensing)
Agency Approvals
Safety: EN50091-1
UL 1778
cUL
EMC:
FCC Part 15 Class A
EN50091-2