20
PP
2VV.
Creating innovative solutions for you and your business since 1995.
ver.1 07-04-20
Control signal options:
0-10V
- 0-10V signal control
On/Off
- On/Off switching
Off/On
- Off/On switching
0-10V + On/Off
- On/Off swi 0-10V signal control
0-10V + Off/On
- Off/On swi 0-10V signal control
CH 10-0V + On/Off
- On/Off swi 0-10V signal control
cooling, heating 10-0V
CH 10-0V Off/On
- Off/On swi 0-10V signal control
cooling, heating 10-0V
08
DX exchanger
19
1.
Min. power for switching the heat pump
2.
Upper output limit 0-10V of HEATER/COOLER output
for requirement state of 0% capacity of the condensing
unit, default = 1V
3.
Max. number of activations of the condensing unit in
ON/OFF mode per hour, range 3 - 60, default = 6
4.
HEAT/COOL delay in output switching, range 1 - 20
minutes, default 3 = minutes
1
4
2
3