Supply Duct Limits
Bypass Temperature
10
11
1. Enable or disable the ventilation level reduction if canal
minimum is not reached (enabled by default)
2. Set maximum canal temperature range of +25 °C to
+45°C.
3. Set minimum canal temperature range of +15 °C to
+20°C.
•
Due to possible condensation on the surface of the ven-
tilation ductwork, it is recommended to leave enabled the
reduction of flow if canal minimum is not reached.
•
Selecting the sensor in the supply ductwork disables the
maximum temperature setting in the ductwork.
1
2
3
Setting of minimum outdoor temperature from which the
bypass opening is allowed (range 0-20°C)
Does not apply to units HR85