48
Table 9-12 instantaneous flow unit
Flow rate Unit
BACNET Enum
m3/h
135
m3/min
165
m3/s
85
L/h
136
L/m
86
L/s
87
Table 9 - 13 heat units
Power Total unit
BACNET Enum
KWh
19
MWh
146
KJ
17
MJ
126(Provisional)
GJ
126(Provisional)
Table 9 - 14 power units
Power rate Unit
BACNET Enum
KW
48
MW
49
kJ/h
17(Provisional)
MJ/h
126(Provisional)
GJ/h
126(Provisional)
Table 9 - 15 temperature units
Temp Unit
BACNET Enum
℃
62
10. Parameter list
10.1 Basic (basic parameter) setting item
Table 10 - 1Basic (basic parameters) setting items
Set item
Description
Options / value
range
Default
value
explain
PV Units
Flow unit
m3/s,m3/m,m3/h,
L/s,L/m,L/h
m3/h
The instantaneous flow data is
displayed
after
conversion
according to this configuration.
Flow
decimals
Flow decimal
point
1,2,3
3
The
decimal
digits
of
the
instantaneous flow data value are
displayed
according
to
this
configuration, but if the integer digit
is too long, the integer digit will be