background image

CB1B1440en / 2013-09-12 

Subject to change 

Siemens Building Technologies 

4/4 

Control parameters 

If you want to change the control parameters, proceed as follows:

 

 

+ / – 

1.  Set the thermostat to Frost Protection mode 

 . 

2.  Press 

+

 and 

 simultaneously for at least 3 seconds. 

Release the buttons and, within 2 seconds, press 

 again for 7 seconds. The display will show "P02". 

3.  Select the required parameter by repeatedly pressing 

+

 or 

 . 

4.  Press 

+

 and 

 simultaneously. The current value of the selected parameter starts to flash. Adjust it by 

pressing 

+

 or 

 . 

5.  Press 

+

 and 

 simultaneously again to display the next parameter. 

6.  If you wish to display and change additional parameters, repeat steps 3 through 5. 
7.  Service or expert level: 10 seconds after the last display or setting, all changes are stored and the 

thermostat will leave the parameter setting mode.  
Expert level: Press 

+

 or 

 until "End" is displayed. Then, press + and – simultaneously to save the change 

and exit the parameter setting mode. 

 

No. 

Thermostat’s parameter 

Factory setting 

Setting range  

 

P02 

Selection of operating mode via operating mode  
button   

1 = Frost Protection – 

Comfort mode 

RDD310/EH: 

1 = Comfort - Frost 

Protection 

2 = Comfort - Economy - 

Frost Protection 

 

RDE410/EH: 

1 = Auto - Comfort - 

Frost Protection 

2 = Auto - Comfort - 

Economy - Frost 
Protection 

 

P05 

Temperature sensor calibration 

0.0 °C 

-3…3 °C 

 

P06 

Standard temperature display 

0 = Room 

temperature 

0 = Room temperature  
1 = setpoint 

 

P08 

Comfort basic setpoint 

20 °C 

5...40 °C 

 

P09 

Min. setpoint limitation in Comfort mode (Wmin

Comf

5 °C 

5...40 °C 

 

P10 

Max. setpoint limitation in Comfort mode (Wmax

Comf

35 °C 

5...40 °C 

 

P11 

Heating setpoint in Economy mode 

16 °C 

Off, 5…18 °C 

 

P14 

Button lock (press operating mode button   for  
3 seconds to lock or unlock) 

0 = Disabled 

0 = Disabled 
1 = Auto lock 
2 = Manual lock 

 

P30 

Switching differential in heating mode 

1 K 

0.5…6 K 

 

P38 

External input 

0 = No input 
1 = External sensor 

input 

 

P45 

Heating system load in kW 

2.8 kW 

0…3.6 kW 

 

P51 

Floor heating temperature limit 

Off 

Off, 10...60 °C 

 

P65 

Setpoint of heating in Frost Protection mode 

 (Wheat

Stb

)  8 °C 

Off, 5…18 °C 

 

P69 

Temporary setpoint in Comfort mode 

Off 

Off = Disabled 
On = Enabled 

 

P71 

Reloading factory settings 

Set value to "On" and confirm by pressing 

+

 and 

  

Off 

Off = Idle 
On = Reset 

 

d02 

Status X1 

Diagnostics 

0…xx °C = Measured 

temperature 

 

d07 

Software version information 

No adjustment 

 

 

(All temperature settings can be made in increments of 0.5 °C with the exception of P51, which is in 1 °C) 

 Please write down all changes you make! 

 
 

1/4 

CB1B1440en / 2013-09-12 

Subject to change 

Siemens Building Technologies 

s

 

 

 

Operating Instructions 

RDD310/EH, RDE410/EH 

 
RDD310/EH and RDE410/EH – the room thermostats for use with electrical floor heating systems. The products feature a 
built-in room sensor to control the room temperature, and the user can connect a cable temperature sensor to limit the 
maximum floor temperature. The thermostat provides Comfort, Economy and Frost Protection mode. The RDE410/EH also 
features an Auto Timer with 8 programmable time switches. You can either rely on the factory settings or make adjustments 
that suit your individual needs. 
 

 

 

Are your rooms too warm or too cold? 

+

 / 

– 

 

Press 

+

 or 

 to increase or decrease the current room temperature setpoint in increments of 0.5  C for 

Comfort mode. 5 seconds after the last push, the room temperature setpoint is automatically saved. The 

display stops flashing and shows the room temperature currently measured. 

The maximum setpoint setting range is 5...40 °C, unless limited by parameters P09 and P10. 

 

Do you require continuous Comfort mode? 

 /   

 

Press the operating mode button 

 to switch to Comfort mode 

. In that case, the room temperature 

setpoint is always maintained at the Comfort level. 
The RDE410/EH has a dedicated   button for selection of the operating mode. 

 

 

D

is

p

la

y

 

O

p

e

ra

ti

o

n

 a

n

d

 s

e

tt

in

g

s

 

 

Buttons locked

 

   Heating demand

 

Measured room temperature, 
setpoints and parameters 

  Symbol when current room 

temperature is displayed 

Current time of day * 

Colder/Warmer

 

Weekday 1…7 (1 = Monday/7 = Sunday)*

 

 

Confirmation

 

of settings

 

 

View and set Auto Timer 
programs

 

 

Frost Protection/  
system On

 

RDD310/EH

 

RDE410/EH

 

* RDE410/EH only 

 

Time of day and weekday 

 

Selection of operating mode 

 

– Auto Timer (

 

– 

Comfort 

(

 

– 

Economy 

(   )

**

 

 

Selection of operating mode

 

 

- Frost Protection (

)  

 

Comfort 

(

 

Economy 

( ) ** 

 

Frost Protection mode 

  Comfort mode 

  Economy mode 

 

Auto Timer mode *

 

Colder/Warmer

 

**  If configured by your HVAC installer 

 

 

 

Summary of Contents for RDD310/EH

Page 1: ...ng and shows the room temperature currently measured The maximum setpoint setting range is 5 40 C unless limited by parameters P09 and P10 Do you require continuous Comfort mode Press the operating mode button to switch to Comfort mode In that case the room temperature setpoint is always maintained at the Comfort level The RDE410 EH has a dedicated button for selection of the operating mode Displa...

Page 2: ...e current weekday 4 Confirm the current weekday by pressing Do you want to set the time switches RDE410 EH only A A A To set the time switches keep the button depressed for 3 seconds to go to Auto Timer mode This mode is indicated by Ax appearing on the display x Auto Timer 1 8 and the time xx xx flashing For each time switch proceed as follows 1 Icons and are displayed Press or to set the Comfort...

Page 3: ...approximate capacity of the heating system in kW via parameter P45 during commissioning The cable temperature sensor is connected to input X1 M and acquires the floor temperature If the floor temperature exceeds the parameterized limit xx ºC P38 1 P51 xx ºC the heating system is turned off until the floor temperature returns to a level below the parameterized limit A typical application are rooms ...

Page 4: ...Comfort Frost Protection 2 Comfort Economy Frost Protection RDE410 EH 1 Auto Comfort Frost Protection 2 Auto Comfort Economy Frost Protection P05 Temperature sensor calibration 0 0 C 3 3 C P06 Standard temperature display 0 Room temperature 0 Room temperature 1 setpoint P08 Comfort basic setpoint 20 C 5 40 C P09 Min setpoint limitation in Comfort mode WminComf 5 C 5 40 C P10 Max setpoint limitatio...