MEDIUM DUTY DOOR OPERATOR

MODELS MT5011U & BMT5011U

INSTALLATION MANUAL

NOT FOR RESIDENTIAL USE

Your model may look different than the model illustrated in this manual.

THIS PRODUCT IS TO BE 
INSTALLED AND SERVICED BY A 
TRAINED DOOR SYSTEMS 
TECHNICIAN ONLY. 

Visit www.liftmaster.com to locate a 
professional installing dealer in your area.

OPERATOR RATING: 

12 cycles per hour, 

50 cycles per day; maximum

Serial # 

(located on electrical box cover)

Installation Date

2 YEAR WARRANTY

Summary of Contents for BMT 5011U

Page 1: ...E Your model may look different than the model illustrated in this manual THIS PRODUCT IS TO BE INSTALLED AND SERVICED BY A TRAINED DOOR SYSTEMS TECHNICIAN ONLY Visit www liftmaster com to locate a professional installing dealer in your area OPERATOR RATING 12 cycles per hour 50 cycles per day maximum Serial located on electrical box cover Installation Date 2 YEAR WARRANTY ...

Page 2: ...INFORMATION Mechanical Electrical ATTENTION AVERTISSEMENT AVERTISSEMENT AVERTISSEMENT WARNING WARNING CAUTION WARNING WARNING AVERTISSEMENT WARNING WARNING WARNING ATTENTION AVERTISSEMENT WARNING CAUTION CAUTION IMPORTANT NOTES BEFORE attempting to install operate or maintain the operator you must read and fully understand this manual and follow all safety instructions DO NOT attempt repair or ser...

Page 3: ...oor height by 2 feet To reduce the risk of SEVERE INJURY or DEATH IMPORTANT INSTALLATION INSTRUCTIONS 1 READ AND FOLLOW ALL INSTALLATION WARNINGS AND INSTRUCTIONS 2 Install door operator ONLY on properly balanced and lubricated door An improperly balanced door may not reverse when required and could result in SEVERE INJURY or DEATH 3 ALL repairs to cables spring assemblies and other hardware MUST ...

Page 4: ... BEARINGS Maintenance Free FINISH Powder coated Corrosion Resistant Steel ELECTRICAL OPERATOR VOLTAGE 115 Vac Single Phase 60 Hz WIRING TYPE C2 Standard B2 configurable see Basic Programming section CONTROL WIRING 16 22 AWG SAFETY DISCONNECT Quick disconnect door arm for emergency manual door operation ENTRAPMENT PROTECTION LiftMaster Monitored Entrapment Protection LMEP Photoelectric Sensors CPS U...

Page 5: ... aglkna gn djkand adgsndajgndoia lajgdajngciosuhadoajdna ld dagjdl abndjnbag duhajbdnkajbn agjdaghadsuabndkjbn dsgakjbndsubhadsjbnakjdbn kgjadkjbagudb kdsjgbsAZdlsuabhdijbadub OP EN OP EN CLOS E CLOS E O STOP STOP NOTE The tracks are shipped separately Actual track length will exceed door height by 2 feet EXAMPLE The track for 12 foot door will be 14 feet OP EN CLOS E O STOP NOT SHOWN Installation...

Page 6: ... holes Install front idler Assemble trolley Track Spacers Track Bolt 3 8 16 x 3 4 Flange Hex Nut Bolt 3 8 16 x 3 4 Flange Hex Nut Trolley Take Up Bolt Hex Nut 3 8 16 Hex Nut 3 8 16 Lock Washer Operator End Header End Track Bolt 3 8 16 x 1 Bolt 3 8 16 x 1 Lock Washer Lock Washer Header End Header End Front Idler 1 2 3 ...

Page 7: ... Operator Header End Operator End Bolt 3 8 16 x 3 4 Bolt 3 8 16 x 3 4 Flange Hex Nut Flange Hex Nut Flange Hex Nut Bolt 3 8 16 x 3 4 Slide trolley onto the track Attach track to operator Track Trolley Operator End ASSEMBLY 4 5 ...

Page 8: ...om of Track Bottom of Track Drive Sprocket Operator Inner Nut 2 Chain Chain ASSEMBLY 6 Wrap chain around front idler in the direction shown 7 Slide trolley 2 inches away from front idler 8 Wrap chain around drive sprocket 9 Attach chain to back of trolley Adjust the chain by tightening the inner nut 10 3 More than 3 ...

Page 9: ...d horizontal line created in step 2 Drill appropriate pilot holes to accommodate mounting hardware 4 10 cm Header Bracket 3 To prevent possible SERIOUS INJURY or DEATH Header bracket MUST be RIGIDLY fastened to structural support on header wall or ceiling otherwise door might not reverse when required DO NOT install header bracket over drywall Concrete anchors MUST be used if mounting header brack...

Page 10: ...possible SERIOUS INJURY from a falling operator Fasten the operator SECURELY to structural supports of the building Concrete anchors MUST be used if installing ANY brackets into masonry ATTENTION AVERTISSEMENT AV A WARNING CAUTION CAUTION PRECAUCIÓN A A ADVERTENCIA 1 Align holes in track with holes in header bracket and secure with cotter pin 2 Nut Nut Nut Lock Washer Lock Washer Lock Washer Bolt ...

Page 11: ...erator could result in electric shock and serious injury DO NOT turn power on until you have finished making ALL power and control wiring connections Maximum wire gauge that can be connected to the operator s terminal is 12 AWG When a larger wire gauge is required the wire must be gauged down to 12 AWG USE COPPER WIRE ONLY Bolt 3 8 16 x 3 4 To reduce the risk of SEVERE INJURY or DEATH ANY maintenan...

Page 12: ...trocution Be sure power is not connected BEFORE installing door control To prevent possible SERIOUS INJURY or DEATH from a closing door Install door control within sight of door out of reach of children at a minimum height of 5 feet 1 5 m and away from ALL moving parts of door Install the control station far enough from the door to prevent the user from coming in contact with the door while operat...

Page 13: ...OPEN Logic Board 3 Button Control Station Connect wires to the control station and replace the control station cover Open Close Stop Control Common Remove factory jumper if external interlock is used TYPICAL INSTALLATION INSTALL 3 BUTTON CONTROL STATION 4 5 Cut this Wire Tie Locate the wire antenna on the outside of the electrical box Cut the wire tie closest to the edge of the electrical box SETU...

Page 14: ...nts are made the entrapment protection device MUST be tested 9 Entrapment Protection device MUST be tested every month 10 ALWAYS KEEP DOOR PROPERLY BALANCED An improperly balanced door may not reverse when required and could result in SEVERE INJURY or DEATH 11 ALL repairs to cables spring assemblies and other hardware ALL of which are under EXTREME tension MUST be made by a trained door systems te...

Page 15: ...tch Decrease Door Travel Increase Door Travel NOTE When retaining plate is released verify that the retaining plate is fully seated with the notches of the limit nut ADJUSTMENT A B Spring Clutch Nut Clutch Nut To Loosen To Tighten ADJUST THE LIMITS Depress retaining plate Adjust OPEN limit Adjust CLOSE limit 1 2 3 Apply power to operator Remove tape holding cotter pin to spring 1 2 3 4 Turn clutch...

Page 16: ...VERTISSEMENT WARNING CAUTION WARNING WARNING WARNING PRECAUCIÓN ADVERTENCIA ADVERTENCIA ADVERTENCIA LIFTMASTER MONITORED ENTRAPMENT PROTECTION LMEP Safety Reversing Sensor Invisible Light Beam Protection Area Safety Reversing Sensor Right Side of Garage Left Side of Garage Photoelectric Sensor 6 15 cm max above floor Invisible Light Beam Protection Area Photoelectric Sensor 6 15 cm max above floor E...

Page 17: ...bstructions are cleared Tighten the nuts securely Inside Wall C Shaped Wrap Mounting Bracket with Square Holes 1 4 20x1 2 Carriage Bolts 1 4 Lock Nuts Drill 3 8 Holes Door Track ALTERNATE WALL INSTALLATION ALTERNATE FLOOR INSTALLATION 2 Discard slotted bracket Drill 3 8 holes in each track and fasten securely with hardware DOOR TRACK INSTALLATION 1 4x1 1 2 Lag Screws 1 4 20x12 Carriage Bolts with ...

Page 18: ...pointing toward each other across the door Attach the sensors to the brackets with the provided hardware Finger tighten the receiving sensor wing nut Securely tighten the sending sensor wing nut Run the wires from both sensors to the operator Use insulated staples to secure wire to the wall and ceiling Connect the sensor wires to the operator 1 2 3 4 Wire Indicator Light C Wrap Wing Nut 1 4 20x1 1...

Page 19: ... connections 10 Factory Wiring Connector Factory wiring harness connection ENTRAPMENT PROTECTION WIRING OPTIONS ENTRAPMENT PROTECTION AUX ANT AUX ANT D14 COM INTRLK STOP LED OPEN CLOSE TTC LEARN 1 LMEP1 LMEP2 2 3 4 5 6 7 STOP CLOSE OPEN AUX ANT AUX ANT D14 COM INTRLK STOP LED OPEN CLOSE TTC LEARN 1 LMEP1 LMEP2 2 3 4 5 6 7 STOP CLOSE OPEN AUX ANT AUX ANT D14 COM INTRLK STOP LED OPEN CLOSE TTC LEARN...

Page 20: ...R MONITORED ENTRAPMENT PROTECTION LMEP DEVICE IS RECOMMENDED A LiftMaster Entrapment Protection LMEP device is required for any momentary contact to close mode of operation including B2 TTC and remote controls NOTES The LED on the logic board will blink once when in C2 and twice when in B2 The operator will automatically convert to B2 wiring when Monitored Entrapment Protection Device is installed...

Page 21: ...ROTECTION DEVICE FACTORY DEFAULT Momentary contact to open and stop with constant pressure to close Open override that reverses when closing by any opening device Wiring for entrapment protection device to reverse NOTE The operator will automatically convert to B2 wiring when Monitored Entrapment Protection Device is installed See accessories page for Monitored Entrapment Protection Devices Timer ...

Page 22: ...K STOP LED OPEN CLOSE TTC LEARN 1 LMEP1 LMEP2 2 3 4 5 6 7 STOP CLOSE OPEN D14 COM INTRLK STOP LED OPEN CLOSE TTC LEARN 1 LMEP1 LMEP2 2 3 4 5 6 7 STOP CLOSE OPEN R27 AUX ANT AUX ANT AUX ANT D14 COM INTRLK STOP LED OPEN CLOSE TTC LEARN 1 LMEP1 LMEP2 2 3 4 5 6 7 STOP CLOSE OPEN D14 COM INTRLK STOP LED OPEN CLOSE TTC LEARN 1 LMEP1 LMEP2 2 3 4 5 6 7 STOP CLOSE OPEN R27 AUX ANT AUX ANT AUX ANT D14 COM I...

Page 23: ...ion Press STOP button The door should stop Press CLOSE button The door should move in the close direction Release CLOSE button Door should stop if in C2 mode The door should continue closing if in B2 mode Press STOP button The door should stop 1 2 3 TEST 3 BUTTON CONTROL STATION 4 5 Press OPEN button The door should open Allow the door to fully open Press CLOSE button The door should close Allow t...

Page 24: ...ess doorway is clear of persons and obstructions ATTENTION AVERTISSEMENT AVE AV WARNING WARNING CAUTION W PRECAUCIÓN AD AD ADVERTENCIA Emergency Disconnect Door Emergency Release Handle Emergency Disconnect Emergency Disconnect Door Arm Door Arm Pull emergency release handle straight down Emergency disconnect will open Lift free end of door arm to trolley Pull emergency release handle to allow arm...

Page 25: ...rol wiring DOOR DRIFTS AFTER OPERATOR STOPS A Door not balanced properly Disconnect trolley assembly and check door for proper operation B Clutch slipping Adjust clutch see ADJUSTMENT section C Brake not functioning properly Check brake mechanism to ensure brake lever is free and brake pads are engaging the brake disc DOOR OPENS CLOSES TOO FAR Limits not adjusted properly Adjust limits See ADJUSTM...

Page 26: ... or shorted close wire 4 Monitored Entrapment Protection Device failure Check for 1 Misaligned or blocked Photoelectric Sensors 2 Issue with Monitored Sensing Edge and or wiring 5 Incorrect motor direction Reverse the yellow and red motor wires on the capacitor 6 Maximum run timer has timed out Maximum run time 90 seconds Check clutch adjustment Door height or speed may exceed the range the operat...

Page 27: ... Button Control Station SECURITY Rugged composite housing Wireless controls cannot be used in place of hard wired controls 1 Button SECURITY Remote Control Includes visor clip Wireless Single Push Button Control SECURITY Rugged composite housing Wireless controls cannot be used in place of hard wired controls 1 2 4 5 7 8 0 3 6 9 333LM WKP5LM3 5 4 digit entry codes WKP250LM3 250 4 digit entry codes...

Page 28: ...NG RETURN TO CENTER AND STOP BUTTON 2 OR MORE KEY LOCKOUT 7 6 3 5 Stop Close Open Stop Close Open 7 6 3 5 Stop Close Open 2 BUTTON STATION OR 3 POSITION KEYSWITCH WITH SPRING RETURN TO CENTER STANDARD 7 6 3 Close Open C2 MODE ONLY 2 OR MORE 7 6 3 Close Open Close Open C2 MODE ONLY DEVICE TO REVERSE EXTERNAL INTERLOCK 1 2 3 4 3 4 Remove Factory Installed Jumper When Interlock is Used ONE 2 OR MORE ...