4

4.  Zurn Gateways have been set to DHCP by default. Please consult 

local IT support for possible additional access requirements for 

your network.

Mounting the Zurn Gateway

The device ships with a mounting bracket. You will also need:

•  Four #6 screws with anchors    •  Screwdriver    •  Drill

Determining Location for the  

Zurn Gateway

•  Select a location central to all devices to be connected to this 

gateway. Place the gateway as high as possible, such as near the 

top of a wall.

•  Avoid obstructions. Thick walls and reflective surfaces, such as metal, 

weaken the signal between the gateway and other devices.

•  Note the LoRa antenna location. 

The signal will be strongest 

radiating from that side of the 

device. The LoRa antenna is 

31.2 mm long.

•  The LoRa antenna is an omni-directional antenna, but for best results, 

mount the device so the LoRa antenna is in a vertical position near 

the top of a wall. We recommend conducting a site survey to test the 

signal strength in different locations before you mount the device.

Mounting the Zurn Gateway

1.  Determine where you want to mount the device.
2.  Mark where you want the screws to go.
3.  Drill holes for the screws and insert anchors.
4.  Place the mounting bracket and secure it 

with screws.

5.  Attach the device to the bracket and rotate  

to lock into place.

Form No. 111-198, 6/19

LoRa  

antenna  
location