Appendix
LM-CIRIA operating and commissioning manual 2.0 | 06. 2012 | en
129
E Factory settings
Path: SERVICE MENU / INTERNAL / CONFIGURATION / MY ADDRESS
Parameter
Value range
Factory setting
ROOM
--; 0 – 99
--
GROUP
0 – 99
0
BUS ADDR.
0 – 99
0
Table 81:
MY ADDRESS
setting options
Path: SERVICE MENU / INTERNAL / CONFIGURATION / WAKE-UP REACTION
TOUCHRING parameter
Description
NO REACTION
The touchring does not function if an absence scene is enabled.
DIMMING
Lighting can be dimmed using the touchring if an absence
scene is enabled, but no scene can be recalled.
DIMMING & SCENE
Lighting can be dimmed and a scene can be recalled using the
touchring if an absence scene is enabled. The SCENE param-
eter defines which scene can be recalled.
Table 82:
TOUCHRING
setting options
Parameter
Value range
Factory setting
SCENE
0 – 20
1
Table 83:
SCENE
setting options
Parameter
Value range
Factory setting
KEY
PRESENCE SCENE;
LAST SCENE
PRESENCE SCENE
Table 84:
KEY
setting options
Path: SERVICE MENU / INTERNAL / CONFIGURATION / ACTION CLICK
Parameter
Value range
Factory setting
LEVEL
0, 1, 2, 3, 4
(0 = no action click,
4 = loud action click)
0
Table 85:
LEVEL
setting options
Path: SERVICE MENU / INTERNAL / CONFIGURATION / SCENE OF KEY
Parameter
Value range
Factory setting
PRESENCE
1 – 20
1
ABSENCE
0 – 20
0
Table 86:
SCENE OF KEY
setting options