Commissioning the field level
LM-CIRIA operating and commissioning manual 2.0 | 06. 2012 | en
108
Setting the fade speed and assigning a building service type
Figure 169:
FADE - TYPE
settings level
–
Start point:
FADE - TYPE
settings level
1. Select
FADE
.
=
FADE
illuminates.
2. Run your finger along the touchring until the desired number appears.
3. Select
TYPE
.
=
TYPE
illuminates.
4. Run your finger along the touchring until the desired setting appears.
5. Select
SAVE
to save the settings.
=
The message
SAVED
briefly appears.
=
Fade speed and building service type are saved.
=
ROOM - GROUP
settings level appears.
Notes
•
Settings are only saved if
SAVE
is selected.
•
Selecting
SAVE
automatically saves all values displayed on the touchscreen.
•
To switch to the
WAITING TIME
settings level directly (without saving), select
NEXT STEP
.
FADE parameter
Value range (in seconds)
Factory setting
FADE
0, 1, 3, 5, 7, 10, 15, 30, 60
0 seconds
Table 66:
FADE
setting options
Building service type
Building service type number
COMMON (all building services)
1
Brightness
2
Blind position
3
Slat angle
4
Screen
10
Colour temperature
13
Window
65
Curtain
64
Temperature
11
Air exchange
39
Table 67: Selection of
TYPE
setting options