Chapter 8

Hardware Installation
Inspection

Table of Contents

Cabinet Inspection......................................................................................................8-1

Power Cable Inspection..............................................................................................8-1

Cabling Inspection......................................................................................................8-2

Label Inspection .........................................................................................................8-2

8.1 Cabinet Inspection

1.

After cabinet installation, the cabinets must be stable and neat. One row of cabinets

must be aligned in one line. The faces of cabinets in one row must be in the same

plane with difference less than 5mm.

2.

Vertical difference of cabinet must be less than 3mm.

3.

All fasteners must be fixed firmly; the length of exposed nuts in the same specification

shall be identical.

4.

All parts on cabinet must be fixed firmly without damage and cables shall be intact

without break; devices shall be labeled completely, correctly and clearly,

5.

After cabinet installation, clean the installation marks on the internal and external

surfaces of the cabinet. The cabinet must be free from dust.

6.

After all cables are laid, the sliding cover plates at the top and bottom cabling holes of

the cabinet must be pushed in position to avoid entry of any animal.

7.

Enclosure in the cabinet and on the work platform must be installed reasonably,

correctly, steadily and firmly.

8.

All cards must be installed correctly and be against the back panel closely. Upper and

lower wrenches on the card must be locked firmly and fixed screws are screwed on.

lank panel must be installed correctly without obvious gap between cards. UN (green)

indicator must be on when system is powered and works normally. ALM (red) indicator

must be on when alarm is generated.

8.2 Power Cable Inspection

l

Power cable

Check if 3-pin plug and 3-core connector at two ends of power cable are correctly and

reliably connected.

l

DC power

8-1

SJ-20110803091932-002|2011-08-30 (R2.0)

ZTE Proprietary and Confidential

Summary of Contents for ZXR10 ZSR

Page 1: ...ulti Service Router Hardware Installation Manual Version V2 8 11 ZTE CORPORATION NO 55 Hi tech Road South ShenZhen P R China Postcode 518057 Tel 86 755 26771900 Fax 86 755 26770801 URL http ensupport zte com cn E mail support zte com cn ...

Page 2: ...ar purpose title or non infringement ZTE CORPORATION and its licensors shall not be liable for damages resulting from the use of or reliance on the information contained herein ZTE CORPORATION or its licensors may have current or pending intellectual property rights or applications covering the subject matter of this document Except as expressly provided in any written license between ZTE CORPORAT...

Page 3: ... 5 3 4 Grounding Inspection 3 5 3 5 Auxiliary Equipment Inspection 3 5 3 6 Required Tools 3 5 3 7 Technical Document Preparation 3 6 Chapter 4 Cabinet Installation 4 1 4 1 Installing a 19 Standard Rack 4 1 Chapter 5 Installing the Worktable 5 1 5 1 Installing the Board 5 1 Chapter 6 Power Cables and Grounding Wires Installation 6 1 6 1 AC Power Cable Installation 6 1 6 2 DC Power Cable Installatio...

Page 4: ... Prolong Cable Installation 7 8 7 6 Fiber Installation 7 8 7 7 V 35 V 24 Cable Installation 7 9 7 7 1 V 35 Cable Installation 7 9 7 7 2 V 24 Cable Installation 7 12 7 7 3 SCSI V 24 Cable Installation 7 20 7 8 Label Style 7 30 Chapter 8 Hardware Installation Inspection 8 1 8 1 Cabinet Inspection 8 1 8 2 Power Cable Inspection 8 1 8 3 Cabling Inspection 8 2 8 4 Label Inspection 8 2 Figures I Tables ...

Page 5: ...quipment installation instruments and necessary technical documents to be used in installation Chapter 4 Cabinet Installation This chapter describes how to install cabinets for ZXR10 ZSR Chapter 5 Power Cables and Grounding Wires Installation This chapter describes the power cables of equipment and their installation process Chapter 6 External Cable Installation This chapter describes installation...

Page 6: ...sult in death or serious injury Warning Indicates a hazard that if not avoided could result in serious injuries equipment damages or interruptions of major services Caution Indicates a potential hazard that if not avoided could result in moderate injuries equipment damages or partial service interruption Note Provides additional information about a certain topic Checkpoint Indicates that a particu...

Page 7: ... or equipment damage Safety precautions introduced in this manual are supplementary to the local safety codes l ZTE bears no responsibility in case of universal safety operation requirements violation and safety standards violation in designing manufacturing and equipment usage 1 2 Safety Description Contents deserving special attention during configuration of ZXR10 ZSR are explained in the follow...

Page 8: ...ZXR10 ZSR Hardware Installation Manual This page intentionally left blank 1 2 SJ 20110803091932 002 2011 08 30 R2 0 ZTE Proprietary and Confidential ...

Page 9: ...ent The installation of ZXR10 ZSR is shown in Figure 2 1 where the continuous thick lines show the parts which are to be installed Figure 2 1 ZXR10 ZSR Installation Sketch Map 2 1 2 Equipment Composition The following devices are needed for configuring ZXR10 ZSR l ZXR10 ZSR main device 2 1 SJ 20110803091932 002 2011 08 30 R2 0 ZTE Proprietary and Confidential ...

Page 10: ...form directly As shown in Table 2 1 ZXR10 ZSR can be configured to the router of different models Table 2 1 ZXR10 ZSR Series Models Model Cabinet Structure Power Supply RA 1809 AC Soho AC RA 1822 AC 1U AC RA 1822 DC 1U DC RA 1822E AC 1U AC RA 1822E DC 1U DC RA 1842 AC 2U AC RA 1842 DC 2U DC RA 1842R AC 1U AC RA 1842R DC 1U DC RA 2822 AC 1U AC RA 2822 DC 1U DC RA 2842 AC 2U AC RA 2842 DC 2U DC RA 2...

Page 11: ...pport both DC and AC power supplies and can provide DC and AC input according to user demands The appearance of ZXR10 ZSR 1U is shown in Figure 2 2 Figure 2 2 ZXR10 ZSR 1U Front View The appearance of ZXR10 ZSR 2U is shown in Figure 2 3 Figure 2 3 ZXR10 ZSR 2U Front View The appearance of ZXR10 ZSR 3U is shown in Figure 2 4 2 3 SJ 20110803091932 002 2011 08 30 R2 0 ZTE Proprietary and Confidential...

Page 12: ...ZXR10 1809 Soho is shown in Figure 2 5 Figure 2 5 ZXR10 ZSR 1809 Soho Front View The appearances of ZXR10 1809 R series products are shown in Figure 2 6 and Figure 2 7 Figure 2 6 ZXR10 ZSR R Compact Model 1U Front View 2 4 SJ 20110803091932 002 2011 08 30 R2 0 ZTE Proprietary and Confidential ...

Page 13: ...00V 240V 50Hz 60Hz Power Supply DC 48V Working Temperature 5 45 Working Humidity 10 90 no dew Table 2 3 Newly Added ZXR10 ZSR Device Parameters Items 1809 Soho 1842R 2842R Series 1U 2882R Series 2U Slot Number 0 4 8 Size mm W H D 180 43 6 330 442 49 400 442 88 400 AC 100V 240V 50Hz 60Hz Power Supply DC 48V Working Temperature 5 45 Working Humidity 10 90 no dew 2 2 Hardware Installation Flow The ha...

Page 14: ...composition l Prepare engineering design documents and installation instruction documents needed for hardware installation l Prepare the necessary installation tools and transport tools l Prepare the necessary certificates and procedures needed for accessing sites For details refer to Chapter 3 Install Main Devices The installation flow of main devices is shown in Figure 2 8 2 6 SJ 20110803091932 ...

Page 15: ...er to Chapter 4 Connect Power Cable As for connection of power cable there are two modes connection of AC power cable and connection of DC power cable For details refer to Chapter 5 Connect Other Cables This part introduces the connection of all cables For details refer to Chapter 6 Check Hardware Installation After all hardware are installed it is necessary to check the installation so as to make...

Page 16: ...ZXR10 ZSR Hardware Installation Manual This page intentionally left blank 2 8 SJ 20110803091932 002 2011 08 30 R2 0 ZTE Proprietary and Confidential ...

Page 17: ...an 1m The space between the face back of the cabinet and wall is not less than 1 5m as shown in Figure 3 1 the cabinet rows in the lab shall be placed separately with aisle between each two not less than 1 2m Figure 3 1 Lab Plane Layout l Load on NOC room floor It must not be less than 450kg per m2 l Net height of the NOC room It must be more than 3 20m if not it must be specified particularly in ...

Page 18: ...r per m2 less than 2mm When raised floor is not available the static conductive floor must be laid the volume resistance must be 1 0x107Ω 1 0x1010Ω The static conductive floor or raised floor must be grounded for static discharge which can be connected with grounding facility through a current limit resistor and connection cable The current limit resistance is 1MΩ 3 2 Indoor Environment of NOC Roo...

Page 19: ...ion is to seal the lab with a shutter equipped with a dust filter device à Work clothes and slippers must be kept clean and changed regularly à It is recommended to place operation equipment in outer room thus avoiding frequent access and opening closing of lab door à Keep a higher relative humidity within the permissible range in the lab to reduce static electricity adsorption of dust à Walls and...

Page 20: ...s or self provided electric generator to supply stable power for air conditioner à Centralized air conditioner or at least two sets of small model air conditioners need to be configured for the lab to provide appropriate temperate for long term operation of devices l Lighting and Illumination Requirements Measures against direct sunshine must be taken to avoid aging and deformation of elements lik...

Page 21: ...arately Electric circuits formed by reinforcing steel bars used in the building or through cabinet are not allowed In case of compound grounding the earthing resistance must be less than 1Ω The cross sectional area of grounding wire is determined by the Max permissible current The grounding wire must be sheathed copper wire instead of bare copper wire 3 5 Auxiliary Equipment Inspection l DDF and O...

Page 22: ...bar and rubber hammer l Common Instruments Multimeter 500V megohmmeter used in insulation resistance measurement l Special Tools à Optical multimeter optical connector and tail fiber à Coaxial trunk self loop cable à Coaxial cable installation tool à Earth resistance tester à Antistatic bracelet ring à Wire stripper à Crimping pliers 3 7 Technical Document Preparation Installation engineering pers...

Page 23: ...in the ventro side of the enclosure and align the screw hole on the enclosure and the flange hole b Use philips screwdriver and special screws to fix the flange to one side of the enclosure c Fix the flange on the other side of the enclosure in above steps 3 Use the philips screwdriver to remove the four gaskets at the bottom of the enclosure and keep them for future use 4 Lift the enclosure slowl...

Page 24: ...ZXR10 ZSR Hardware Installation Manual Figure 4 1 Enclosure Installation 4 2 SJ 20110803091932 002 2011 08 30 R2 0 ZTE Proprietary and Confidential ...

Page 25: ...ing the Board ZXR10 ZSR provides three enclosure models 1U 2U and 3U 1 As for 1U enclosure there are two slots for line interface card LIC The slot numbers are LIC1 and LIC2 from top to down 2 As for 2U enclosure there are four slots for LIC The slot numbers are LIC1 LIC4 in sequence of from left to right and from top to down 3 As for 3U enclosure there are eight slots for LIC The slot numbers are...

Page 26: ... system and can not be used While ZXR10 ZSR can be compatible with LIC cards ending with other characters or without special identifiers And these LIC cards can be used 5 2 SJ 20110803091932 002 2011 08 30 R2 0 ZTE Proprietary and Confidential ...

Page 27: ... cable One end is connected to AC power socket on AC power module of ZXR10 ZSR and the other end is connected to 220V AC power socket Figure 6 1 AC Power Cable 6 2 DC Power Cable Installation As shown in Figure 6 2 the model of ZXR10 ZSR DC power cable is C PWR 074 Figure 6 2 DC Power Cable Connector of End A is 042051000017 which is a D model solder plug for 3 conductor straight cable Hole Pin Ho...

Page 28: ...ice and three terminals on terminal B shall be connected according to labels pasted on each conductor where B1 is connected to DC power supply 48V GND B2 is connected to DC power supply 48V B3 is connected to Protective Earth PE 6 3 Grounding Wire Installation There is a grounding screw on the back of ZXR10 ZSR enclosure and the screw is on the left bottom For using yellow green cabinet protect ca...

Page 29: ...e l Optical fiber l V 35 V 24 cable 7 2 Configuration Cable Installation 7 2 1 Console Cable Installation Serial console cable is the basic cable used to configure and maintain ZXR10 ZSR The model is C 232 007 One end of the cable is the DB9 female plug connected to the serial interface on background terminal The other end of the cable is RJ45 connector connected to the CONSOLE port on front panel...

Page 30: ...4 White 7 6 Green 2 7 White 8 8 Brown 1 The following shows how to use CAT5 twisted pair cable to make serial console cable l Strip 20mm external insulation away from both ends of cable and strip 3mm of core wire l Solder the core wire to corresponding pin of DB9 plug as required in the table above The soldering must be firm and reliable l Install the shell of DB9 and the cable mustn t get loose l...

Page 31: ... and hyper CAT5 network cables are often used as network cables RJ45 plugs are crimped on both ends of the cable with the structure as shown in Figure 7 2 Figure 7 2 Structure Of Network Cable With RJ45 Connectors At Both Ends The cable is 8P8C straight cable solder plug the specification is E5088 001023 technical parameters rated current 1 5 rated voltage 125V crimped with AWG24 28 wire gauge rou...

Page 32: ...ge 3 2 Orange 6 3 White and Green 1 6 Green 2 4 Blue 4 5 White and Blue 5 7 White and Brown 7 8 Brown 8 7 4 E1 Cables Installation ZXR10 ZSR provides many kinds of channelized E1 cards which use different interfaces and cables 7 4 1 120Ω Twisted Pair Installation 8 4 port channelized E1 interface card RA 8CE1 RA 4CE1 provides a RJ48 socket and can be connected with 120Ω balanced twisted pair cable...

Page 33: ...o converter through coaxial cable The connection relationship of the straight through E1 cable ends is shown in Table 7 6 Table 7 6 Connection Relationship of RJ48 Connectors at Two Ends of Straight through E1 Cable Terminal A Signal Terminal B Signal 1 RX_RING 1 TX_RING 2 RX_TIP 2 TX_TIP 3 Un connected 3 Un connected 4 TX_RING 4 RX_RING 5 TX_TIP 5 RX_TIP 6 Un connected 6 Un connected 7 Un connect...

Page 34: ... 1 RX END IB 2 OA 8 3 TX END OB 17 IA 18 RX END IB 31 OA 7 32 TX END OB 4 IA 5 RX END IB 19 OA 6 20 TX END OB 36 IA 35 RX END IB 34 OA 5 33 TX END OB 6 IA 7 RX END IB 4 21 TX END OA 4 22 TX END OB 8 IA 9 RX END IB 23 OA 3 24 TX END OB 38 IA 37 RX END IB 40 OA 2 39 TX END OB 7 6 SJ 20110803091932 002 2011 08 30 R2 0 ZTE Proprietary and Confidential ...

Page 35: ... 3 75Ω Coaxial Cable Installation 4 port channelized E1 non balanced micro coaxial interface card RA 4CE1 75 provides BNC interface and can be connected with 8 core micro coaxial cable As the eight single core cables are in the same one sheath the lengths of the eight single core cables have been adjusted to match the sockets on the backplane Connect the cables as shown in Figure 7 3 7 7 SJ 201108...

Page 36: ...XR10 ZSR is USBAM and the other end is USBAFM The example is shown in Figure 7 4 Figure 7 4 USB Extension Cable Note The USB extension cable is universal for data products 7 6 Fiber Installation In ZXR10 ZSR different optic interface cards provide different types of optical interfaces including SC LC and MT RJ Except for MT RJ whose RX and TX ends are integrated in one physical interface the RX an...

Page 37: ...o position horizontally according to idle slot ID on the module and interface card Force plugging unplugging is forbidden Two types of fibers are available single mode fiber and multi mode fiber User can configure the fiber according to the actual application Generally multi mode fiber is used in short distance transmission while single mode fiber is used in long distance transmission As for fiber...

Page 38: ...e B 6 Blue F 6 Blue F 2 2 3 2 and 3 of Termi nal A Short Cir cuited 3 11 and 12 of Ter minal A Short Circuited C C C and D of Termi nal B2 Short Cir cuited D C and D of Termi nal B1 Short Cir cuited D 4 White H 4 White H 5 Orange E 5 Orange E 7 White W 7 White W 8 Green U 8 Green U 9 White P 9 White P 19 Brown S 19 Brown S 20 Red M 20 Red M 21 Blue N 21 Blue N 22 Red R 22 Red R 23 Orange T 23 Oran...

Page 39: ...ion of V 35DA cable is shown in Table 7 9 Table 7 9 V 35DA Cable Connection Terminal A D36 Plug Cable Chro matogram Terminal B2 V 35 plug pin Terminal A D36 Plug Cable Chro matogram Terminal B1 V 35 plug pin 1 White B 10 White B 4 Blue EF 13 Blue EF 2 11 3 2 and 3 of Termi nal A Short Cir cuited 12 11 and 12 of Ter minal A Short Circuited C C C and D of Termi nal B2 Short Cir cuited D C and D of T...

Page 40: ... 30 Blue V 22 Red P 31 Red P 23 Orange S 32 Orange S 24 Red BB 33 Red BB 25 Green Z 34 Green Z 26 Red W 35 Red W 27 Brown U 36 Brown U 7 7 2 V 24 Cable Installation V 24AA V 24AA cable is used when the serial interface card is used as DTE in V 24 service The figure is shown in Figure 7 7 Figure 7 7 V 24AA Cable The connection of V 24AA cable is shown in Table 7 10 7 12 SJ 20110803091932 002 2011 0...

Page 41: ...r cuited 5 1 White 7 10 White 7 4 Blue 20 13 Blue 20 5 White 6 14 White 6 6 Orange 8 15 Orange 8 7 Green White 24 16 Green White 24 9 Brown White 2 18 Brown White 2 20 Blue Red 23 29 Blue Red 23 22 Orange Red 3 31 Orange Red 3 24 Green Red 17 33 Green Red 17 26 Brown Red 15 35 Brown Red 15 V 24BA V 24BA cable is used when the serial interface card is used as DCE in V 24 service The figure is shown...

Page 42: ...of Terminal B1 Short Circuited 5 5 White 20 14 White 20 6 Orange 20 15 Orange 20 7 Green White 15 16 Green White 15 9 Brown White 3 18 Brown White 3 20 Blue Red 17 29 Blue Red 17 22 Orange Red 2 31 Orange Red 2 24 Green Red 24 33 Green Red 24 26 Brown Red 24 35 Brown Red 24 V24A RJ45 Cable Reverse Telnet One end of V24A RJ45 cable is the MDR 36 plug and the other end are two RJ45 connectors The fi...

Page 43: ...LK1 8 Brown TCLK1 9 Black Grey 2 TXD1 RXD1 6 19 White V35TXD1 20 Grey RCLK1 21 Red RCLK1 22 Blue RXD1 TXD1 3 23 Red V35RXD1 24 Orange ECLK1 25 Red ECLK1 26 Green ECLKA1 27 Red Brown V35ECLKA1 D36 Plug RJ45 Connector Terminal B1 10 Black Grey GND GND 5 11 White RTS0 Note 1 12 Blue CTS0 Note 1 13 White DTR0 14 Orange DSR0 15 White CD0 GND 4 Note 1 16 Green TCLK0 17 White TCLK0 18 Brown TXD0 RXD0 6 2...

Page 44: ...ECLKA0 36 Green V35ECLKA0 Note Connect pins 4 and 5 of RJ45 rather than connect GND cables of M_CD and RJ45 connectors of MDR 36 plug V24A DB9 Cable Reverse Telnet One end of V24A DB9 cable is the MDR 36 plug and the other end are two DB9 connectors The figure is shown in Figure 7 10 Figure 7 10 V24A DB9 Cable The connection of V24A DB9 cable is shown in Table 7 13 7 16 SJ 20110803091932 002 2011 ...

Page 45: ...CLK1 8 Brown TCLK1 9 Black Grey 2 TXD1 RXD1 2 19 White V35TXD1 20 Grey RCLK1 21 Red RCLK1 22 Blue RXD1 TXD1 3 23 Red V35RXD1 24 Orange ECLK1 25 Red ECLK1 26 Green ECLKA1 27 Red Brown V35ECLKA1 D36 Plug DB9 Female Plug Terminal B1 10 Black Grey GND GND 6 11 White RTS0 Note 1 12 Blue CTS0 Note 1 13 White DTR0 14 Orange DSR0 15 White CD0 GND 5 Note 1 16 Green TCLK0 17 White TCLK0 18 Brown TXD0 RXD0 2...

Page 46: ... ECLK0 35 Yellow ECLKA0 36 Green V35ECLKA0 Note Connect pins 4 and 5 of DB9 rather than connect GND cables of M_CD and DB9 connectors of MDR 36 plug MODEM Cable One end of MODEM cable is the MDR 36 plug and the other end are two DB25 male plugs The figure is shown in Figure 7 11 Figure 7 11 MODEM Cable The connection of MODEM cable is shown in Table 7 14 7 18 SJ 20110803091932 002 2011 08 30 R2 0 ...

Page 47: ...K1 ETC1 24 8 Brown TCLK1 9 Black Grey 2 TXD1 TD1 2 19 White V35TXD1 20 Grey RCLK1 ERC1 23 21 Red RCLK1 22 Blue RXD1 RD1 3 23 Red V35RXD1 24 Orange ECLK1 RC1 17 25 Red ECLK1 26 Green ECLKA1 TC1 15 27 Red Brown V35ECLKA1 D36 Plug 0 45kg DB25 Male Plug 10 Black Grey GND GND 7 11 White RTS0 Note 1 RTS0 Note 1 4 12 Blue CTS0 Note 1 CTS0 Note 1 5 13 White DTR0 DTR0 20 14 Orange DSR0 DSR0 8 15 White CD0 ...

Page 48: ... together which indicates that they are in pair l Black Grey indicates that the conductor is the Black one in Black and Grey cable pair Correspondingly Grey Black indicates this conductor is the Grey one in Black and Grey cable pair l CTS of this card is provided by RTS of this card Peer CTS is provided by peer RTS 7 7 3 SCSI V 24 Cable Installation V 24 DS 001 V 24 DS 001 cable is used when RA 8A...

Page 49: ...inal A Cable Chro matogram Terminal B Signal at Terminal B 37 White 7 GND 53 White 7 GND 2 Note Blue 4 Note RTS0 18 Note Blue 4 Note RTS4 39 Note White 5 Note CTS0 55 Note White 5 Note CTS4 36 Orange 20 DTR0 52 Orange 20 DTR4 5 White 6 DSR0 21 White 6 DSR4 4 Green 8 CD0 20 Green 8 CD4 3 White 2 TD0 19 White 2 TD4 38 Brown B1 3 RD0 54 Brown B5 3 RD4 7 21 SJ 20110803091932 002 2011 08 30 R2 0 ZTE Pr...

Page 50: ...Note RTS2 26 Note Blue 4 Note RTS6 47 Note White 5 Note CTS2 63 Note White 5 Note CTS6 44 Orange 20 DTR2 60 Orange 20 DTR6 13 White 6 DSR2 29 White 6 DSR6 12 Green 8 CD2 28 Green 8 CD6 11 White 2 TD2 27 White 2 TD6 46 Brown B3 3 RD2 62 Brown B7 3 RD6 49 White 7 GND 65 White 7 GND 14 Note Blue 4 Note RTS3 30 Note Blue 4 Note RTS7 51 Note White 5 Note CTS3 67 Note White 5 Note CTS7 48 Orange 20 DTR3...

Page 51: ...e 7 16 Table 7 16 V 24 DS 002 Cable Connection Terminal A Cable Chro matogram Terminal B Signal at Terminal B Termi nal A Cable Chro matogram Terminal B Signal at Terminal B 37 White 7 GND 53 White 7 GND 2 Note Blue 5 Note CTS0 18 Note Blue 5 Note CTS4 39 Note White 4 Note RTS0 55 Note White 4 Note RTS4 36 Orange 8 CD0 52 Orange 8 CD4 5 White 6 DSR0 21 White 6 DSR4 4 Green 20 DTR0 20 Green 20 DTR4...

Page 52: ...Note CTS2 26 Note Blue 5 Note CTS6 47 Note White 4 Note RTS2 63 Note White 4 Note RTS6 44 Orange 8 CD2 60 Orange 8 CD6 13 White 6 DSR2 29 White 6 DSR6 12 Green 20 DTR2 28 Green 20 DTR6 11 White 3 RD2 27 White 3 RD6 46 Brown B 3 2 TD2 62 Brown B7 2 TD6 49 White 7 GND 65 White 7 GND 14 Note Blue 5 Note CTS3 30 Note Blue 5 Note CTS7 51 Note White 4 Note RTS3 67 Note White 4 Note RTS7 48 Orange 8 CD3 ...

Page 53: ... 7 14 V 24 DS 003 Cable Connection of V 24 DS 003 is shown in Table 7 17 Table 7 17 V 24 DS 003 Cable Connection Termi nal A Cable Chro matogram Terminal B Signal at Terminal B Terminal A Cable Chro matogram Terminal B Signal at Terminal B 37 White 7 GND 53 White 7 GND 2 Blue 18 Blue 39 White 55 White 36 Orange 52 Orange 5 White 21 White 4 Green 20 Green 3 White 6 RD0 19 White 6 RD4 38 Brown B1 3 ...

Page 54: ...0 Blue 26 Blue 47 White 63 White 44 Orange 60 Orange 13 White 29 White 12 Green 28 Green 11 White 6 RD2 27 White 6 RD6 46 Brown B3 3 TD2 62 Brown B 7 3 TD6 49 White 7 GND 65 White 7 GND 14 Blue 30 Blue 51 White 67 White 48 Orange 64 Orange 17 White 33 White 16 Green 32 Green 15 White 6 RD3 21 White 6 RD7 50 Brown B4 3 TD3 66 Brown B 8 3 TD7 SCSI 68 Plug and DB9 Female Plug Multi Core Cable One end...

Page 55: ...CSI 68 Plug DCE Signal Direction DB9 Female Plug Terminal B1 Pin No Conductor Color Schematic Diagram Signal Name Conductor Signal Name Pin No 37 GND0 GND0 6 2 M_RTS0 39 M_CTS0 36 M_DTR0 5 M_DSR0 4 M_CD0 GND0 5 Note 1 3 M_TX0 RD0 2 38 M_RX0 TD0 3 SCSI 68 Plug DB9 Female Plug Terminal B2 41 GND1 GND1 5 6 M_RTS1 43 M_CTS1 40 M_DTR1 SCSI 68 Plug DB9 Female Plug Terminal B2 7 27 SJ 20110803091932 002 ...

Page 56: ...rminal B3 45 GND2 GND2 6 10 M_RTS2 47 M_CTS2 44 M_DTR2 13 M_DSR2 12 M_CD2 GND2 5 Note 1 11 M_TX2 RD2 2 46 M_RX2 TD2 3 SCSI 68 Plug DB9 Female Plug Terminal B4 49 GND3 GND3 6 14 M_RTS3 51 M_CTS3 48 M_DTR3 17 M_DSR3 16 M_CD3 GND3 5 Note 1 15 M_TX3 RD3 2 50 M_RX3 TD3 3 SCSI 68 Plug DB9 Female Plug Terminal B5 53 GND4 GND4 6 18 M_RTS4 55 M_CTS4 52 M_DTR4 21 M_DSR4 20 M_CD4 GND4 5 Note 1 19 M_TX4 RD4 2...

Page 57: ...8 Plug DB9 Female Plug Terminal B6 56 M_DTR5 25 M_DSR5 24 M_CD5 GND5 5 Note 1 23 M_TX5 RD5 2 58 M_RX5 TD5 3 SCSI 68 Plug DB9 Female Plug Terminal B7 61 GND6 GND6 6 26 M_RTS6 63 M_CTS6 60 M_DTR6 29 M_DSR6 28 M_CD6 GND6 5 Note 1 27 M_TX6 RD6 2 62 M_RX6 TD6 3 SCSI 68 Plug DB9 Female Plug Terminal B8 65 GND7 GND7 6 30 M_RTS7 67 M_CTS7 64 M_DTR7 33 M_DSR7 32 M_CD7 GND7 5 Note 1 31 M_TX7 RD7 2 66 M_RX7 ...

Page 58: ... corresponding name is parallel network cable à Port A is the terminal A of cable plug which is corresponding to terminal B or another terminal à 5m is the finished cable length which is the straight length from plug of cable at one end to the plug of cable at the other end à FE 10 100Base T 1 indicates connection position which is the first network interface of the fast Ethernet interface card 10...

Page 59: ... transverse English label affects the cable s appearance It is pasted on the cable through the self contained cellulose tape l Labels Pasted on Cables à Power Cable Label A flag type label worked out by ZTE can be used as an engineering marker for power cables as shown in Figure 7 18 Figure 7 18 Power Cable Label The paste position is 2cm from the lug Firstly paste the label on the cable for less ...

Page 60: ...If the other end is power distribution cabinet the characters distribution cabinet and the characteristics of the power cable must be indicated For example Distribution GND Note The contents on two labels at two ends of a power cable must be opposite to each other For example the contents filled in L area of the label at one end must be consistent with those filled in R area of the label at the ot...

Page 61: ...1 Meaning and Composition of Coaxial Cable Engineering Label Both sides of the coaxial cable label are marked with L and R The specific meanings are as follows t When label is stuck to coaxial cable on ZXR10 ZSR side The R side of the label must be filled with the actual content of the DDF row and column numbers of the DDF the layer of the cable in the DDF and cable number In this case the row num...

Page 62: ...ZXR10 ZSR Hardware Installation Manual Figure 7 22 Transverse English Type 1 Label 7 34 SJ 20110803091932 002 2011 08 30 R2 0 ZTE Proprietary and Confidential ...

Page 63: ...ks on the internal and external surfaces of the cabinet The cabinet must be free from dust 6 After all cables are laid the sliding cover plates at the top and bottom cabling holes of the cabinet must be pushed in position to avoid entry of any animal 7 Enclosure in the cabinet and on the work platform must be installed reasonably correctly steadily and firmly 8 All cards must be installed correctl...

Page 64: ... cable clips must be bound in the same direction and with even space l When cable is laid in horizontal cabling channel bind one cable clip at each cable hole along the cable channel l When cable is laid in vertical cabling channel bind one cable clip every 80 space l Cable must be laid at the specific positions with consistent binding space l Cables must be laid smoothly and mustn t be crossed bi...

Page 65: ...Serial Console Cable 7 2 Figure 7 2 Structure Of Network Cable With RJ45 Connectors At Both Ends 7 3 Figure 7 3 8 core Micro Coaxial Cable 7 8 Figure 7 4 USB Extension Cable 7 8 Figure 7 5 V 35C Cable 7 10 Figure 7 6 V 35DA Cable 7 11 Figure 7 7 V 24AA Cable 7 12 Figure 7 8 V 24BA Cable 7 13 Figure 7 9 V24A RJ45 Cable 7 14 Figure 7 10 V24A DB9 Cable 7 16 Figure 7 11 MODEM Cable 7 18 Figure 7 12 V ...

Page 66: ...re Installation Manual Figure 7 20 Meaning and Composition of Fiber Engineering Label 7 32 Figure 7 21 Meaning and Composition of Coaxial Cable Engineering Label 7 33 Figure 7 22 Transverse English Type 1 Label 7 34 II ...

Page 67: ...le 7 5 Connection Relationship at the Ends of E1 Crossover Cable RJ48 7 5 Table 7 6 Connection Relationship of RJ48 Connectors at Two Ends of Straight through E1 Cable 7 5 Table 7 7 Line Order at DB44 Interface 7 6 Table 7 8 V 35C1 Cable Connection 7 10 Table 7 9 V 35DA Cable Connection 7 11 Table 7 10 V 24AA Cable Connection 7 13 Table 7 11 V 24BA Cable Connection 7 14 Table 7 12 V24A RJ45 Cable ...