SLAVING DAMPERS
Slaving More Than Three Zone Dampers
Slaving Up To Three Zone Dampers
GEN III
– VVT
STMPD or STCD damper without damper control board
WST or WCD damper
C
C
R
R
RX
RX
TX
TX
MC
RO
RC
C
AUX
MC
RC
RO
ZONE DAMPER 1
ZONE DAMPER 4
MC
RO
RC
ZONE DAMPER 2
MC
RO
RC
ZONE DAMPER 3
MC
RO
RC
24 VOLT
TRANSFORMER
CONTROL
RELAY
SPST
CONTROL
RELAY
SPST
STMPD or STCD damper without damper control board
WST or WCD damper
Up to three dampers can be directly controlled by one GEN III damper control board. The first damper must be a WST
round or WCD rectangular damper, slave dampers will be STMPD round or STCD rectangular dampers without damper
control boards. To wire two or three dampers for a zone, use the following wiring diagram. Remember to size the power
transformer for the total number of zone dampers in the system, 2VA per damper
When slaving more than three zone dampers, use the following diagram. An additional 24-volt transformer and control
relays are needed for these applications.
Note: All slave dampers need to be model STMPD / STCD
C
C
R
R
RX
RX
TX
TX
MC
RO
RC
C
AUX
MC
RC
RO
ZONE DAMPER 3
MC
RO
RC
ZONE DAMPER 2
MC
RO
RC
ZONE DAMPER 1
40