Wire Unit to GEN III Controller
Using standard 18 ga. thermostat wire, connect GEN III unit outputs to HVAC unit. Standard HVAC
control terminal designations are used, R Y1 Y2 W1(O/B) W2 G, and energize HVAC unit.
1. Gas/Electric Wiring
Gas/Electric systems use the same terminal designations, R power (24 volt), Y1 Cooling first stage, Y2
Cooling second stage, W1 Heating first stage, W2 Heating second stage and G Fan. From the GEN III
controller, wire each required terminal, R on GEN III to R on HVAC unit, Y1 on GEN III to Y1 on HVAC unit,
Y2 on GEN III to Y2 on HVAC unit (if used) the W1 on GEN III to W1 on HVAC unit, W2 on GEN III to W2 on
HVAC unit (if used) and G on GEN III to G on HVAC unit.
2. HEAT PUMP Wiring— O/B operation
Heat Pump systems use the following terminal designations, R power (24 volt), Y1 Compressor first stage,
Y2 Compressor second stage, O/B (W1) reversing valve, W2 Heating Auxiliary (3) stage, G Fan. From the
GEN III controller, wire each required terminal, R on GEN III to R on HVAC unit, Y1 on GEN III to Y1 on
HVAC unit, Y2 on GEN III to Y2 on HVAC unit (if used), O/B (W1) on GEN III to O on HVAC unit, W2 on GEN
III to W2 on HVAC unit (if used) and G on GEN III controller to G on HVAC unit.
Note: 1. Many systems are single stage and will not use Y2 or W2 terminals for operations.
Please confirm your system operation to ensure proper wiring.
2. For Heat Pump applications with Gas/Electric inputs, set system for gas operation and reset high limit to 115 degrees.
GEN III CONTROLLER
POWER SWITCH
ID / SYNC
24VAC IN
24VAC OUT
TO UNIT TERMINALS
RS485 COMMUNICATION LINK ( BELDEN 8740)
AUX SENSOR (AS)
LEAVING AIR SENSOR (LVAIR)
OUTSIDE AIR SENSOR (OA)
RETURN AIR SENSOR (RA)
INSTALLATION INSTRUCTIONS
GEN III
– VVT
INSTALLATION INSTRUCTIONS
STATUS LIGHTS
10