MASTER CONTROL
09
FAN MODE
SET FAN OPERATION
EXIT
AUTO
While in SYSTEM CONFIGURATION menu, press
Down
and press
SELECT
on the
(9) FAN MODE menu item, (instructions above).
Use the
up
or
Down
to set the Fan Mode to AUTO or ON.
Press
Exit
to return to the System Configuration screen.
Press
yes
to save the settings
.
Fan operation is configured for either Fan ON or AUTO. When system is configured for
ON operation, the Fan will run during Occupied Schedule and will revert to Auto
operations during unoccupied schedule. When system is configured for Auto
operation, Fan will only run when there is a call for heating or cooling.
10
UNIT TYPE
While in SYSTEM CONFIGURATION menu, press
Down
and press
SELECT
on the
(10) UNIT TYPE menu item, (instructions above).
Use the
up
or
Down
to set the desired Unit Type for each thermostat
Select
Gas, Heat Pump OBO, Heat Pump OBB, Electric
.
Note: Some heat pump units use GAS/ELECTRIC inputs – confirm your unit’s operation to ensure
proper configuration.
SET UNIT TYPE
Press
Exit
to return to the System Configuration screen.
Press
yes
to save the settings
.
12
MAVERICK
ENABLE/DISABLE
MAVERICK
Maverick operations allow the system to recognize an outlier call in the system. When
most zones in a system are calling for heat and 1 zone is calling for cooling, the system
will initiate a MAVERICK CALL protocol by starting a time clock. Logic in the controller
will provide a time period for first calls to satisfy, then run a purge cycle and then
maverick call. Maverick call will remain on until zone is satisfied, then run purge and
return to majority operations.
EXIT
ON
OFF
While in SYSTEM CONFIGURATION menu, press
Down
and press
SELECT
on the
(12) MAVERICK menu item, (instructions above).
Select
On
to enable Maverick or
Off
to disable.
If ON is selected, press the
up
or
Down
buttons to select the period 15-30 minutes.
Press
Exit
to return to the System Configuration screen.
Press
yes
to save the settings
.
11
SYNC
MONITOR
SYNCHRONIZE MONITOR
SAVE SETTINGS
SAVE SETTINGS
Note: Only one thermostat in a system can be an enabled Monitor Thermostat.
All other stats will review only.
While in SYSTEM CONFIGURATION menu, press
Down
and press
SELECT
on the
(11) SYNC THE MONITOR menu item, (instructions above).
Press
yes
to Sync Monitor or
no
to Exit.
If yes is selected, do not exit this screen. You will need to press the SYNC button on
the GEN III controller and allow the thermostat to sync in Monitor mode.
Press
Exit
to return to the System Configuration screen.
Press
yes
to save the settings
.
YES
SYNC MONITOR?
NO
EXIT
UNIT TYPE
GAS
2) LOCK
HEAT PUMP OBO
HEAT PUMP OBB
ELECTRIC
MAVERICK - DISABLE
SELECT
The GEN III is designed as a universal GAS/ELECTRIC/HEAT PUMP Controller. Factory
default is set for GAS operations, and may require field configuration when applying this
product to Electric or Heat Pump applications.
Each system has one thermostat which operates as the Monitor Thermostat for
the system. This thermostat must be synchronized with the GEN III control board.
TO ENTER
System Configuration
Press and hold the
Menu
followed by the
SET
button simultaneously until System Configuration is displayed.
Then use the Up and Down button to scroll through the system configuration options.
31