17
NUMBER
OF DAMPERS
Press the
up
or
Down
button to increase/decrease number of dampers for this
installation.
Press
Exit
button.
Press
yes
to save the settings.
EXIT
NUMBER OF DAMPERS
09
While in SYSTEM CONFIGURATION menu, press
Down
and press
SELECT
on the
(17) NUMBER OF DAMPERS menu item, (instructions above).
SELECT
NUMBER OF DAMPERS
Press the
up
or
Down
button to increase or decrease OFFSET.
Adjust /- X degrees and wait until the offset values returns back to 00 on its
own. After the offset returns to 00, the new LAT value will also be displayed. You
can continue to adjust the offset again if necessary.
Note: If 00 does not appear after your adjustment, the LAT update has not been
saved. Please wait until 00 appears to confirm this adjustment.
Press
Exit
button - Allow up to 2 minutes for CALIBRATION reset in system.
18
LAT
CALIBRATION
EXIT
LAT CALIBRATION
LEAVING AIR:
ADD OFFSET:
48
00
While in SYSTEM CONFIGURATION menu, press
Down
and press
SELECT
on the
(18) LAT CALIBRATION menu item, (instructions above).
LAT CALIBRATION
Installer should set the number of dampers in the system. This reduces the
time needed for the GEN III controller to poll and review each zone’s
needs. Installer can set the number of zones from 1-20.
LAT is calibrated at the factory, however in shipping and installation, calibration may
become skewed. If calibration is needed, use a thermometer to find reference
temperature next to LAT in supply duct, and follow the steps below to set an offset
for LAT from Monitor Stat.
Press the
up
or
Down
button to ENABLE or DISABLE.
Press
Exit
button.
Press
yes
to save the settings.
19
MORNING
WARM UP
EXIT
MORNING WARM UP
ENABLE
While in SYSTEM CONFIGURATION menu, press
Down
and press
SELECT
on the
(19) MORNING WARM UP menu item, (instructions above).
MORNING WARM-UP
In cold climates a MORNING WARM UP sequence will assist in preheating the building
prior to occupancy. The GEN III system provides a strategy for morning warm up based
on a sophisticated algorithm built into the system controller. When enabled, the system
will switch from Unoccupied to Occupied two hours prior to system start time and run
heating for 20 minutes to evaluate time needed to raise building temperature, after 20
minutes system will return to Unoccupied mode. Using the information gathered from
the 20-minute warm up evaluation, thermostats will reset individual occupied start times
to provide morning warm up for each zone in the building.
TO ENTER
System Configuration
Press and hold the
Menu
followed by the
SET
button simultaneously until system configuration is displayed.
Then use the up and down button to scroll through the system configuration options.
33