background image

             Form 2263-110506                             MMP2 Installation and Operating Instructions                           ©2017 ZONEFIRST

®

 

 

Leaving Air Sensor

(Mounted in Supply Air before Zone Dampers)

Model ZPS

LAS Terminals
On Zone Panel

 

 
NOTE:  If the ZPS is not used, the NO SENSOR jumper located just above 
the LAT terminals must be on the pins. 
 

After installing the ZPS, use the chart supplied with the  ZPS to check the 
Ohm reading for the appropriate duct temperature.    

 

TROUBLESHOOTING 

The  MMP2  is  a  very  simple  control  to  troubleshoot,  especially  with  the 
LED indicators.  The only other device needed is a simple Volt/Ohm meter.   
 
Almost all problems can be traced to an external component or wiring to 
the  MMP2.      While  the  MMP2  has  been  designed  to  operate  under 
extreme  voltage  conditions  and  is  fuse  protected,  like  any  computer  the 
micro-processor can hang up and not operate properly. 

    

Turn off the power to the panel for several seconds until the LEDs got out 
and  then  turn  the  power  back  on  to  see  if  the  panel  resets.    In  many 
instances this resolves the problem.   
 
The first check is for 24VAC Power to the panel.  When there is power the 
Green Power LED will be lit.  If not check the transformer and the power 
supply to it.   
 

 
 
Zone(s) Not Calling 

Each zone has a Green LED next to the zone relay when it is calling.  The 
LED  being  lit  shows  that  the  call  is  being  recognized  by  the  MMP2.    If  a 
zone is supposed to be calling and the Zone LED is not on, check for 24VAC 
across the thermostat terminal C and the Y, if a Cool call, W if a Heat Call, 
or G if a Fan call.  If there is no voltage here at the panel the panel is not 
getting  the  signal  from  the  thermostat.    The  problem  is  mis-wiring,  a 
broken  wire  or  a  problem  in  the  thermostat.    To  check  the  zone  on  the 
panel, place jumper from R to Y to simulate a Cool call, R to W to simulate 
a Heat call, or  R to G  to simulate a  Fan call.   By jumping these terminals 
the zone LED will activate.     
 

 
Zone(s) Will Not Shut Off 

If a zone will not stop calling, the Zone LED should still be on.  Depending 
on the call disconnect the Y, W or G wire from the zone terminal strip on 
the panel.  The call from that zone will drop out when the thermostat wire 
is  removed.    Check  the  thermostat  wiring  for  a  mis-wiring  or  short  that 
keeps the zone calling.   
 
 
If  the  thermostat  wire  is  disconnected  from  the  proper  terminal  on  the 
zone  and  the  zone  LED  remains  lit,  re-boot  the  panel  to  see  if  the  call 
drops.  If the call still stays on, turn power off to the panel for 10 seconds 

and  then  turn  back  on.    Once  power  is  restored  and  the  thermostat  is 
disconnected the call should drop from the zone, if not replace the panel.   
 

 
Damper Motor Checkout Procedure 

In  order  to  determine  the  operation  of  the  damper  motors,  the  panel 
motor plug can be checked to determine if power is being supplied from 
the  panel.    If  there  is  power  at  the  motor  plug,  the  problem  may  be  a 
broken wire or poor connection in the cord or the motor itself.   
 
To  check  the  power  to  the  motor  from  the  damper  plug  on  the  panel, 
switch  your  meter  to  DC  Volts.    Note  the  wires  on  the  plug  and  check 
across  either  Positive  and  Negative  wires.    Note  that  each  plug  has  two 
positive  leads  and  two  negative  leads.    Both  positive  and  both  negative 
leads are wired together.  The meter will read either Plus (+) or Minus (-) 
12VDC depending if the damper is to be Open or Closed respectively.  
 
 
 
 
DAMPER CLOSED 

-12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

VDC

-12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

-12VDC

-12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

VDC

 

 
 
DAMPER OPEN 

+12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

VDC

+12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

+12VDC

+12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

VDC

 

 
When  using  multiple  dampers  on  a  single  zone,  please  note  to  have  no 
more  than  10  dampers  on  a  single  zone.      Adding  dampers  beyond  the 
recommended number may cause all dampers to be slow to operate and 
may not fully cycle between open and closed.   
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 

Reviews: