background image

             Form 2263-110506                             MMP2 Installation and Operating Instructions                           ©2017 ZONEFIRST

®

 

 

 
 
 
 
WIRING  

The MMP2 is very simple to wire and requires only a minimum number of 
connections.  The MMP2 terminal blocks are screw-less and all wires can 
easily be pushed into their respective terminal by de-pressing the button 
for each point and releasing once the wire is seated.  To remove the wire, 
just press its button again and remove the wire.     
 

Zone  Dampers

 

  The  MMP2  powers  only  the  12VDC  plug-in  dampers.   

Each damper comes with a modular cord and plugs (RJ11) already installed 
to allow each zone damper to just plug into the MMP2 panel.  Additional 
dampers  can  be  slaved  to  one  another  by  using  the  dual  ports  (inter-
changeable)  on each  MP12  actuator.    Additional  dampers are  connected 

“daisy c

hain

ed”

 from one damper to the next.  A maximum of 10 dampers 

per zone is recommended.   
 
Upon installation it is recommended that as each motor is connected that 
each motor is cycled, before connecting the next motor, to insure proper 
operation  of  that  motor  and  to  minimize  troubleshooting  looking  for  a 
possible bad motor or wire connection.   

 
 
Plug-In Damper Wiring 

 

To Additional Dampers

Up to 10 Per Zone, if used.

Zone Damper

Connector on 

Zone Panel

NOTE: It does NOT matter which jack on damper    

goes to the panel or additional dampers.  

PLUG-IN ZONE DAMPER 

25 Foot Modular Cord

(Provided with each damper)

 

 
 
 

 
Zone Thermostats

 

 The thermostats wiring for single stage can be four or 

five  wire.    The  fifth  wire  being  the  C-Common  terminal  for  24  Volt 
powered  thermostats.    There  are  5  terminals  on  the  MMP2  for  each 
thermostat, marked Y-G-R-W-C.  This wiring is shown on Wiring Diagram 1 
for single stage thermostats.     
 

 

Zone Thermostat Wiring 

 

 

G

Y

R

W

C

ZO

NE 

T

HER

MOS

T

A

T

G

Y
R

W

C

70°

ZONE THERMOSTAT

 

 
 
 
 
 

 
 
 
 
HVAC Equipment

 

 The HVAC equipment will follow Wiring Diagram 2 for 

Single  Stage  Systems.      The  MMP2  can  also  control  Heating  Only  and 
Cooling Only as well as both Heating and Cooling.   

HVAC Equipment Wiring 

 

Y  COMPRESSOR RELAY

G         FAN RELAY

W      HEAT RELAY

R   24V. TRANSFORMER   C

FURNACE CONTROLS

OUTDOOR CONDENSING UNIT

Y

G

W

R

EQUIPM

ENT

 

 
 
 

 
Transformer

 

 A separate 24 Volt AC, 40VA Transformer is recommended 

to  power  the  control  panel,  thermostats  and  dampers.    Often  the 
transformer on the HVAC unit only has enough power for its own controls.  
Therefore  it  is  recommended  a  separate  transformer  be  used  to  power 
this panel and the dampers wired to it.   

 
Transformer Wiring 

 
 

24V 

T

R

A

N

S

C
R

C
R

T24 -24V 40VA

TRANSFORMER

 

 
 
Zone Plenum Sensor 

The Zone Mix-Air Sensor, Model ZPS, is a remote sensor that is located in 
the supply air duct to sense the leaving air temperature of the HVAC Unit.  
The ZPS is a high limit protection for the heating and a low limit protection 
for  the  cooling.    When  zoning,  the  airflow  through  the  HVAC  Unit  is 
critical.  The ZPS protects the equipment in low air flow situations as well 
as when by-pass air is being directed back into the return air duct.   
 
The heating limit is fixed at 170

F.  The cooling limit is fixed at 40

F.  When 

the ZPS senses heating above its set point, or cooling below its set point, 
the MMP2 will drop both stages of heating or cooling.  The ZPS must sense 
a  10

F  fall  for  heating  or  rise  for  cooling  before  re-activating  the  first 

stages of heating or cooling.  

 

The  ZPS  requires  2  wires  from  the  sensor  to  the  LAT  terminals  on  the 
MMP2 panel.  The ZPS probe can also be adjusted for length by loosening 
the end nut and sliding the probe thru the mounting plate in order for the 
probe to pass through any duct insulation 

 

Reviews: