Combined Signal Automaton 10+SGA 

for the release of the sound and light signals 

of whistle, signal lamp, bell and gong 

4/5 

 
 
 

Maintenance 
 
The Signal Automaton 10+SGA is maintenance-free. 
 
Power  supply  from  board  mains  must  be  disconnected  whenever  carrying  out  installation  or 
repair work. 
 
Signal durations are works adjusted in conformity  with Rule 34 and 35 of the COLREG 1972 . 
Alteration of signal duration or program release or the programming of special signals may only 
be carried out by skilled personnel. 

 

 
 
Trouble shooting and fault deletion 
 
Manual signal release is not possible and key illumination fails. 
 
1.  Check correct connection of terminals 2+3 to power supply indicated on the name plate

 
2.  Check fuses F1 and F2 which are accessible from the reverse of the signal automaton. 
    As replacement only use fine wire fuses 2A, semi-time lag, 250 V, 5 x 20 mm. 
 
3.  If above measures lead to no result, membrane keyboard, control PCB, power supply PCB 

can easily be replaced. For this purpose first remove the front frame and then the terminal 
strips on the reverse of the signal automaton. Then unloose the 4 screws in the front plate 
and remove it forwards. The front plate carries the PCBs.

 

07.12 Pi 

ZÖLLNER - KIEL

 

01808851.06-4e 

Subject to alteration! 

Summary of Contents for Signal Automaton 10+SGA

Page 1: ...g system separate push buttonkeys signal intervals adjustable dimmer for key illumination latest technical standard made in Germany functional membrane keyboard self explanatory symbols installation o...

Page 2: ...omatic on off Regel rule 35a b c e g Automatic on off Regel rule 35g bell gong 144 Warnsignal attention Steuerbord starboard Backbord port R ckw rts astern Horn whistle Licht general alarm abandon shi...

Page 3: ...or audio Gener al Alar m Exter n Stop Gen Al PA System 1 Bell Gong 11 12 Abandom Ship GA signal output f or lamp ZB110 ZG110 01506539 4 MH 05 13 or muting S R D Manual Alar m Bell Gong 1 muting Whistl...

Page 4: ...1 Bell Gong 11 12 1 muting SRD ZB110 ZG110 01506540 4 MH 05 13 or muting S R D 1phase...

Page 5: ...aneuver is finished the off key O must be pushed for switching off 4 Rule 34 d When vessels in sight of one another are approaching each other and from any cause either vessel fails to understand the...

Page 6: ...signal SOS repeated continuously 11 Signal MOB man over board three prolonged blasts in succession repeated continuously Additional acoustic and optic signals can be released manually by at will push...

Page 7: ...ivated by external push button 3rd key switching on off of automatic bell and gong signals in restricted visibility Rule 35 g Activation of this function is indicated by a red LED next to the key Sign...

Page 8: ...l Trouble shooting and fault deletion Manual signal release is not possible and key illumination fails 1 Check correct connection of terminals 2 3 to power supply indicated on the name plate 2 Check f...

Page 9: ...age 90 264 V AC 24 V DC 50 60 Hz 2 Horizontal or vertical installation is possible 3 For mechanical installation a cutout of 139 x 139 mm in the bridge console is necessary Plug in depth is 120 mm 3 1...

Page 10: ...ng off 4 Rule 34 d When vessels in sight of one another are approaching each other and from any cause either vessel fails to understand the intentions or actions of the other or is in doubt whether su...

Page 11: ...repeated continuously 11 Signal MOB man over board three prolonged blasts in succession repeated continuously Additional acoustic and optic signals can be released manually by at will push buttons Ope...

Page 12: ...g signals in restricted visibility Rule 35 g Activation of this function is indicated by a red LED next to the key Signal keys in 2nd row from left to right 1st key all manual sound signals 2nd key sw...

Page 13: ...ing and fault deletion Manual signal release is not possible and key illumination fails 1 Check correct connection of terminals 2 3 to power supply indicated on the name plate 2 Check fuses F1 and F2...

Page 14: ...DC 50 60 Hz 2 Horizontal or vertical installation is possible 3 For mechanical installation a cutout of 139 x 139 mm in the bridge console is necessary Plug in depth is 120 mm 3 1 The automaton is in...

Page 15: ...V 17100095 4d e 03 13 MH 10 SGA Art Nr 0171610...

Reviews: