background image

7

© Copyright 2018 Zoeller

®

 Co. All rights reserved.

Indoor Prepackaged System Installation Instructions

This set of instructions is for factory prepackaged indoor systems only. If your system is a field assembled indoor 

system, use these instructions as a guideline. If your system is an outdoor system then go to the next section in this 

manual that covers outdoor systems.

 

 1.  Indoor grinder pump systems are for installing at grade in an indoor 

application only. If you will be installing this system outside next 

to the residence then you will need an outdoor system.  DO NOT 

INSTALL THE INDOOR SYSTEM OUTDOORS.

  2.  Review the drawing in Fig. 5 on page 6 and the actual system to 

become familiar with the components in the grinder pump system.  

Review where the unit will be installed.  Determine where the power 

feed, inlet pipe, discharge pipe and vent will be located.

  3.  Remove the unit from the packing.  Indoor prepackaged systems 

are preassembled at the Zoeller Company and require a minimum 

of field assembly work.  All work inside the basin can be performed 

via the inspection port. There should be no reason to remove the 

cover from the basin. Pump and float switches are already set 

inside the basin.

  4.  Remove the inspection plate from the cover.  All floats are set and 

tethered for proper operation from the factory. Verify that where the 

float switches are set will work for your application. Verifying that 

the float switches are set properly and will not hang up inside the 

basin is the responsibility of the installing contractor. Float switches 

are tied in place for shipping purposes. Cut the cable tie around 

each float switch bulb or the unit will not operate properly.

  5.  Dig a hole for the basin. The basin should be located in a very low 

traffic area within 15’ of the power disconnect.  The hole should be at 

least 8” larger in diameter than the basin in order to leave 4” of backfill 

all the way around the perimeter. A minimum of 4” of compacted 

subbase is also required.  Backfill and subbase should be 1/8” to

 

3/4” pea gravel or 1/8” to 1/2” crushed stone. Also reference the 

basin installation instructions included with the unit.

  6.  The 4” inlet hub should be located between the top lip of  the basin 

and the alarm float “on” level with a minimum distance of 10 inches 

between the floor of the basin and hub. Determine the location of 

the inlet hub based upon your inlet pipe arrangement. The inlet 

hub must be used with 4” pipe.  It is best to install the inlet on the 

side of the basin opposite the float switches. Most systems are 

supplied with a field installed 4" pipe seal inlet fitting. This inlet 

fitting is installed in the basin's side-wall in a 5" hole drilled with a 

hole saw at a location lining up with the inlet pipe.

  7.  Set the basin in the hole and connect the 4" inlet pipe to the inlet 

hub using the rubber insert. Backfill around the basin with specified 

media. Care should be taken not to damage components or leave 

voids when backfilling. Finish grade of floor should be poured in 

place around the top 6” of the basin assembly.

  8.  Connect the discharge pipe, valves and vent according to all 

applicable National, State and Local plumbing codes.

  9.  Mount the control panel on the wall within 15’ of  the system.  

Connect the float switch and pump cords.

10.  Clean any debris out of the basin. Fill the basin with water and 

check the system for proper operation.

11.  Record system start-up data for future reference.

12.  Seal and secure the inspection plate to the lid using the proper 

bolts and sealant. Pouring concrete around the system can now 

be completed. 

Summary of Contents for BA7011

Page 1: ...LL cause serious personal injury death or major property damage Warns of hazards that CAN cause serious personal injury death or major property damage Warns of hazards that CAN cause personal injury or property damage INDICATESSPECIALINSTRUCTIONSWHICHARE VERY IMPORTANT AND MUST BE FOLLOWED THOROUGHLY REVIEW ALL INSTRUCTIONS AND WARNINGS PRIOR TO PERFORMING ANY WORK ON THIS PUMP MAINTAIN ALL SAFETY...

Page 2: ... warranty does not apply to and there shall be no warranty for any material or product that has been disassembled without prior approval ofManufacturer subjectedtomisuse misapplication neglect alteration accidentoractofGod thathasnotbeeninstalled operatedormaintained inaccordancewithManufacturer sinstallationinstructions thathasbeen exposed to outside substances including but not limited to the fo...

Page 3: ... that float control switches will not hang up on the grinder pump or other pit peculiarities and are secured so that the grinder pump will shut off It is recommended to use rigid pipe and fittings and the pit be 24 in diameter for simplex systems and 36 in diameter for duplex systems or larger 4 Grinderinstallationsshouldbecheckedyearlyfordebrisand orbuild up which may interfere with the ON or OFF...

Page 4: ...em installation 3 All electrical connections including pump to control box and power supply to control panels must comply with the National Electrical Code and applicable local codes Conduit and panel enclosure openings must have a gas and watertight seal Installation of electrical panels conduit and connections should be made by a qualified licensed electrician AULListed potting kit P N 10 2350 i...

Page 5: ...ectrical shock Do not remove the power supply cord and strain relief or connect conduit directly to pump Installation and checking of electrical circuits and hardware should be performed by a qualified licensed electrician FIGURE 2 LEAD IDENTIFICATION WIRING DIAGRAM SINGLE PHASE 2 BHP MODEL 7011 SK1367 009048 THREE PHASE MODELS 7011 7012 7013 FIGURE 4 FIGURE 3 L1 START RELAY START CAPACITOR GREEN ...

Page 6: ...d All installations must comply with all applicable electrical and plumbing codes including but not limited to the National Electrical Code local regional and or state plumbing codes etc Indoor Prepackaged System FIGURE 5 SK1695 36 48 60 24 NOMINAL ...

Page 7: ...ly 5 Dig a hole for the basin The basin should be located in a very low trafficareawithin15 ofthepowerdisconnect Theholeshouldbeat least8 largerindiameterthanthebasininordertoleave4 ofbackfill all the way around the perimeter A minimum of 4 of compacted subbase is also required Backfill and subbase should be 1 8 to 3 4 pea gravel or 1 8 to 1 2 crushed stone Also reference the basin installation in...

Page 8: ...GLASS AFD 1 25 2 Z RAIL 2 CAST IRON CHECK VALVE 3 4 GUIDE RAILS 2 SCH 80 BALL VALVE 2 FLEX BOOT FITTING LOCATION VARIES WITH BASIN DEPTH FLOAT TREE ASSEMBLY 2HP GRINDER PUMP 2 PVC SCH 80 PLBG 1 8 302 STAINLESS STEEL LIFTING CABLE ALARM ON OFF SOLID FIBERGLASS COVER HIGH WATER ALARM OR SIMPLEX CONTROL PANEL FIELD INSTALLED ALARM FLOAT SWITCH MUST OPERATE OFF LOW VOLTAGE TO BE USED WITH QWIK BOX SK3...

Page 9: ...in the basin s side wall in a 5 hole drilled with a hole saw at a location lining up with the inlet pipe 6 The bottom of the excavation can now be properly backfilled compactedandleveled Setbasininhole Ensuretheremovable cover extends above the finished grade line and the grade slopes awayfromtheunit Backfillandsubbaseshouldbe1 8 3 4 pea gravel or 1 8 1 2 crushed stone Reference basin installation...

Page 10: ...talled Floats positioned properly Discharge valves open 3 16 vent hole drilled in pipe between check valve and pump Once the above has been verified proceed with the following checks Pump power cables and control floats properly installed and voltage verified Conduit connections to panel and junction box are properly sealed After installing the pump into the containment area with adequate submerge...

Page 11: ...the spacer shims located behind the star cutter 5 Remove the three cap screws holding the disc and remove disc from the pump 6 The disc and star cutter can be replaced with new service partsorresurfacedbygrinding Resurfacingisaccomplished by surface grinding both disc and star cutter to a 32 micro finish Do not attempt grinding in the field Send parts to a qualified machine shop or return to the f...

Page 12: ...ring insulated protective sole shoes and not standing in water Under flooded conditions contact your local electric company or a qualified licensed electrician for disconnecting electrical service to the pump prior to removal Grinder pumps contain oil which becomes pressurized and hot under operating conditions Allow 2 1 2 hours after shut down before servicing pump Condition Common Causes A Pump ...

Reviews: