2.4 I Option connection
2.4.1 "Heating priority" option (depending on model)
•
This function allows the unit to start the filtration (in 5 minutes cycle every 220 minutes) to detect the water
temperature and thus switch on the filt heating unit to maintain this temperature at a constant value. It is
said that the filtration pump is slaved to the heating system. Filtration is maintained or put into operation if the pool
temperature is below the required temperature.
•
For the connection, connect the filtration timer to terminals 1 and 2 and add a shunt between terminals 3 and 4.
1
2
1- 2 : power for the filtration pump power contactor coil
: filtration timer
: power contactor (tripolar or bipolar) for the filtration system
pump motor
: separate cable for the "heating priority" function
: heat pump terminal (see wiring diagram § “5.3 I Wiring
diagram”)
: fuse
•
Modification of the time between 2 filtration operations (value in number of minutes):
- press and
or
at the same time for 3 seconds:
appears,
- press
until the
parameter appears, then press
or
to change the parameter using
the
and
keys.
-
Once the value has been modified, press
or
to confirm,
- press to exit the menu.
2.4.2 "Remote control" option (depending on model)
•
This option enables the device's user interface to be duplicated to enable the device to be controlled by remote. To
do so, use the remote control kit available as an accessory.
•
For the connection, consult the manual supplied with the kit.