background image

2

WARNINGS CONCERNING APPLIANCES CONTAINING REFRIGERANT

• 

R290 refrigerant is classed under category A3 as highly flammable.

• 

The appliance must be stored in a room without any permanent ignition source 

(such as open flames, operating gas appliance or operating electric heating).

• 

Do not use means for accelerating the defrosting or cleaning process other than 

those recommended by the manufacturer.

• 

No not perforate or incinerate.

• 

Please note that R290 refrigerant may give off a certain odour.

INSTALLATION AND MAINTENANCE

• 

The appliance may not be installed close to combustible materials, or the air duct 

inlet of an adjacent building.

• 

With some appliances, it is essential to fit a "protection grid"-type accessory if the 

unit is installed in an area with uncontrolled access.

• 

During installation, troubleshooting and maintenance, pipes may not be used as 

steps:  the  pipe  could  break  under  the  weight,  spilling  refrigerant  and  possibly 

causing serious burns.

• 

When servicing the appliance, the composition and state of the heat transfer fluid 

must be checked, as well as the absence of any traces of refrigerant.

• 

During maintenance work, ensure there are no traces of corrosion or oil around 

the cooling components.

WARNINGS ASSOCIATED WITH ELECTRICAL APPLIANCES

• 

The power supply to the appliance must be protected by a dedicated 30 mA Residual 

Current Device (RCD), complying with the standards and regulations in force in the 

country in which it is installed.

• 

Do  not  use  any  extension  lead  when  connecting  the  appliance;  connect  the 

appliance directly to a suitable power supply.

• 

Before carrying out any operations, check that:

 

- The  required  input  voltage  indicated  on  the  appliance  information  plate 

corresponds to the mains voltage;

 

- The  mains  supply  is  compatible  with  the  appliance's  electricity  needs  and  is 

correctly grounded.

• 

In the event of abnormal operation or the release of odours from the appliance, 

turn it off immediately, unplug it from its power supply and contact a professional.

• 

Before  servicing  or  performing  maintenance  on  the  appliance,  check  that  it  is 

powered  off  and  completely  disconnected  from  the  power  supply.  Moreover, 

check  that  the  heating  priority  (where  applicable)  is  deactivated  and  that  any 

other device or accessory connected to the appliance is also disconnected from 

the power supply.

• Do not disconnect and reconnect the appliance to the power supply when in 

operation.

• 

Do not pull on the power cord to disconnect it from the power supply.

• 

If the power cord is damaged, it must be only replaced by the manufacturer, an 

authorised representative or a repair shop.

• 

Do not perform maintenance or servicing operations on the appliance with wet 

hands or if the appliance is wet.

• 

Before connecting the appliance to the power supply, check that the connection 

unit or socket to which the appliance will be connected is in good condition and 

shows no signs of damage or rust.

• In stormy weather, disconnect the appliance from the power supply to prevent it 

from suffering lightning damage.

• 

Do not immerse the appliance in water or mud.

• 

Always unplug the device from the mains when it is not in use. 

EN

Summary of Contents for DT850E

Page 1: ...H0369900_REVC 2021 01 More documents on www zodiac com DT 850 E EN Instructions for installation and use English Dehumidifier Translation of the original instructions in French...

Page 2: ...ledge and experience unless they receive supervision or prior instructions on using the appliance from a person responsible for their safety Children must be supervised to ensure that they do not play...

Page 3: ...ny extension lead when connecting the appliance connect the appliance directly to a suitable power supply Before carrying out any operations check that The required input voltage indicated on the appl...

Page 4: ...thermo dynamic and acoustic performance LABELLING The equipment must be labelled so as to specify that it is out of order and that the refrigerant has been drained The label must be dated and signed F...

Page 5: ...st be carried out before returning the compressor to the supplier Only the electric heater of the compressor body can be used to accelerate this process This operation can be carried out safely once a...

Page 6: ...nciple 10 3 2 I User interface presentation 10 3 3 I Starting the appliance 11 Maintenance 12 4 1 I Maintenance 12 Troubleshooting 15 5 1 I Appliance behaviour 15 5 2 I Electrical diagram 15 Tip to ma...

Page 7: ...1 1 I Description DT 850 E Anti vibration studs round Anti vibration studs rectangular Screw Plugs Mounting bracket Included 1 2 I Dimensions and marking 750 mm 345 mm 660 mm Suction grid Blower grid...

Page 8: ...ound pressure at 1 m db A 20 Approximate weight kg 37 Cooling fluid R290 Cooling fluid load kg 0 3 Service pressure min max bar 8 5 22 MPa 0 85 2 2 Operating range of pool room C 7 35 Protection ratin...

Page 9: ...s pool room high relative humidity During building make sure that the materials used are compatible with a swimming pool environment the walls are sufficiently waterproofed and insulated to prevent co...

Page 10: ...acket and the appliance to avoid vibrations spreading through the wall Fix the 2 supplied round anti vibration studs in the intended locations at the bottom corners of the appliance s rear panel Faste...

Page 11: ...work with impedance under 0 095 ohm The power supply must correspond to the voltage indicated on the appliance s information plate The power cord must be insulated against any cutting or hot elements...

Page 12: ...ation see 2 1 3 Connecting the condensate drainage line After a 5 minute delay if the level of ambient humidity is higher than the desired humidity level the compressor starts up and the COMP indicato...

Page 13: ...create a fire or explosion risk All possible ignition sources in particular cigarettes must not enter within a sufficient perimeter of the installation repair removal or disposal site in the event tha...

Page 14: ...ed The leak detection equipment must be adjusted to a percentage of the refrigerant s LFL and must be calibrated according to the refrigerant used The appropriate gas percentage 25 at most must be con...

Page 15: ...fill the cylinders no more than 80 of the volume must be filled with liquid 9 Do not exceed the maximum working pressure of the cylinder even temporarily 10 When the cylinders have been filled correct...

Page 16: ...dynamic principle which transforms part of the absorbed energy into heat which is then transferred to the ventilated air flow The appliance begins defrost ing The dehumidifier s cooling circuit is aff...

Page 17: ...5 2I Sch ma lectrique Electricaldiagram Schaltplan Bedradingschema Esquemael ctrico Esquema el ctrico Schema elettrico...

Page 18: ...or L ftermotor Motor ventilator Motor ventilador Motor ventilador Motore ventilatore C1 Condensateur ventilateur Fan capacitor L fterkondensator Condensator ventilator Condensador ventilador Condensad...

Page 19: ...rty of their respective owners Votre revendeur Your retailer Mod le appareil Appliance model Num ro de s rie Serial number Pour plus d informations enregistrement produit et support client For more in...

Reviews: