Configure AD module channel data.
⚫
Data value model, namely, correspond to 4 channels of AD module.
AD Module
CH3
CH2
CH1
CH0
Value (16 hexadecimal)
8
4
2
1
⚫
The meaning of each data value:
Data Value
Range Type
0
All channels are OFF.
1
Channel 0 is ON.
2
Channel 1 is ON.
3
Channel 0 and channel 1 are ON.
4
Channel 2 is ON.
5
Channel 0 and channel 2 are ON.
6
Channel 1 and channel 2 are ON.
7
Channel 0, 1, 2 are ON.
8
Channel 3 is ON.
9
Channel 0 and channel 3 are ON.
10
Channel 1 and channel 3 are ON.
11
Channel 0, 1, 3 are ON.
12
Channel 2 and channel 3 are ON.
13
Channel 0, 2, 3 are ON.
14
Channel 1, 2, 3 are ON.
15
All channels are ON.
(6000 +
10*
expansion
submodule
address) h
00h
IN_GENERIC
1
1
UNSIGND8
RO
⚫
The number of default subindex, the fixed value is 1.
⚫
Expansion submodule address: the nearest expansion submodule
address to coupler is 0, addresses of following other modules
accumulate in order, namely, 0, 1, 2, 3…
01h
IN_GENE_INT1
0
0x0000
~0xFFFF
UNSIGND16