Pellet burner „GP 32”
Potentiometer number
Number
of LED
blinking
P1 P2 P3 P4 P5
[-]
Operating period
[seconds]
Index
0 30
1.50
30 45 0
1 45
1.65
60 90 1
2 60*
1.82
90 135 2
3 75
2.18
120
180 3
4 90
2.83
150*
225 4
5 105
3.68
180
270 5
6 120
4.79
210
315 6
7 135
6.22
240
360 7*
8 150
7.46
270
405 8
9 165
8.21
300
450* 9
Table 5.2.
Description of the operating parameters of the burner’s control
board of pellet burner type “
GP 32
” (the nominal thermal capacity is
32kW)
.
NOTES :
●
the values, indicated with this symbol “
*
” show the default (factory
preset) values of the operating parameters, which in most cases will
guarantee reliable and effective operation of the burner;
●
A good criteria for the efficient operation of the burner is the color of the
flame. When the flame’s color is dark yellow, some smoke is visible as
well, then in most of the cases the fuel rate is higher that optimal and it
should be decreased by changing the position of the thermal capacity
potentiometer. The increase of the air flow rate also influences the