SU-S: E032 – INTERCEPTOR STROKE TOO BIG

POSSIBLE CAUSES AND CORRECTIVE ACTIONS

 

,QVXI²FLHQWSRZHUVXSSO\

 

NOTE: E032 due to poor power supply will effect all servo units!

  1. 

Check battery and/or charger condition to ensure the supply delivers the expected power. 

  2. 

Check power supply connections and verify that all cables have the correct dimensions 

 

   

(wire diameters shall be 12 AWG or larger).

  3. 

Verify power supply is not connected via automatic thermal/magnetic fuses.

  4. 

Connect Zipwake directly to a new separate battery to completely rule out the power supply as    

 

   

cause of failure. 

 

(OHFWULFDOIDLOXUHRI686

  1. 

Rule out power supply issue (see previous check-list).

  2. 

Check if the SU-S that reports error operates (makes any movement) at system turn on.

  3. 

Replace SU-S if confirmed it is not operating.      

 

6HUYRXQLW¬VVFUHZVKDIWKDVEURNHQ

  1. 

Restart the system and listen for the SU-S operating at system turn on (or when powered up as    

 

   

connected to the DU-S). A screw shaft failure is suspected if the SU-S runs for a longer period

 

   

(a couple of seconds) than normal, followed by the error code E032.

  2. 

Disconnect servo unit from the interceptor back plate and check the movement of screw shaft and  

 

   

nut when motor is running. If the shaft/nut is not moving or can be visually confirmed to be

 

   

broken, replace the servo unit. 

  The electronics sense the electrical motor operates out of range,

  primarily occurs in connection to system startup.

ERROR CODE TRIGGER

6

Summary of Contents for S Series

Page 1: ...TROUBLE SHOOTING GUIDE...

Page 2: ...TROUBEL SHOOTING GUIDE DYNAMIC TRIM CONTROL SYSTEM SERIES S Release R1A April 2019 Language English Copyright 2019 Zipwake AB Sweden All rights reserved www zipwake com...

Page 3: ...r individual sets of error codes bit encoded The Distribution Unit DU S do not generate any error codes Presence of system error is indicated in the CP S display by a flashing red info symbol in combi...

Page 4: ...er cooler location 64 GPS error No GPS signal Check GPS source and GPS status on the Select GPS source menu page norm set to Auto GPS signal is acquired received If an external GPS or NMEA 2000 GPS is...

Page 5: ...d check that the blades are moving correctly run Interceptor Check 64 Electronics failure Electronics failure Restart the system power turned on main switch toggle Visit www zipwake com for upgrades r...

Page 6: ...supply issue see previous check list 2 Check if the SU S that reports error operates makes any movement at system turn on 3 Replace SU S if confirmed it is not operating 6HUYR XQLW V VFUHZ VKDIW KDV E...

Page 7: ...ase of any indication the blades are obstructed Interceptor Check readout not in the green range check for excessive marine growth dirt paint or sealant on interceptor s moving parts 2 Remove the Inte...

Page 8: ...DFKHG GXULQJ 68 6 VWDUWXS VHTXHQFH 1 Remove any obstacles growth dirt mud paint etc that prevents the interceptor blade to fully retract 2 Check and verify the SU S is mounted with the screw shaft nut...

Page 9: ...1 Check that the system units listed in the CP S under System Information agrees with the actually connected units 2 Check cable and connectors for dirt or damage Try connecting SU S to a different c...

Page 10: ...onnect all units in the system except one CP S connected to the DU S on the I BUS OUT connection 2 Connect the SU S units one by one to the DU S at PORT3 connection and identify which SU S that trigge...

Page 11: ...h designated torque 5 Nm Run the Interceptor Check and verify that the blades are moving freely within tolerance range all the readings of Interceptor Check are in green range Document and archive the...