Installation instructions & user manual
T210023 v1.02 NOV 2018 - ZIP AP430S-AP4100S
Technical support
Tel: 0345 6 005 005 email: service@zipindustries .co.uk www.zipwater.co.uk
Installation
Connection to the electricity supply
• Before connecting to the power supply network,
install a power supply cord in the water heater,
with a min. diameter of 1.5 mm
2
(H05VV-F 3G 1.5
mm
2
).
• To do this, the protective plate must be removed
from the Aquapoint.
• Switch off the mains electrical supply before
removing the electrical cover panel or carrying
out any work involving a live circuit or access to
components that may be live.
• Do not switch on the electrical supply until the
Aquapoint is full of water.
• This Aquapoint must be earthed.
• The electrical connection to the heating elements must conform to current IEE wiring
regulations and be permanently connected to the electrical supply through a double-pole
isolating switch with at least 3mm contact separation in each pole and with a minimum
rating of 13A.
•
All internal wiring is factory mounted and should not be altered or modified.
• A suitable supply cable should be fed through the grommet on the underside of the
Aquapoint, connected to the live, neutral and earth connections on the terminal block and
secured with the cable clamp provided.
• Check all electrical connections for security and tightness.
•
An over temperature cut-out is incorporated within the Aquapoint which is designed to
operate at 79 - 84ºC. Should this happen, press the reset button.
IMPORTANT
•
Before resetting the over temperature cut-out, isolate the electrical supply to the Aquapoint
(prior to removing the electrical cover panel).
•
Ensure that the cover panel is replaced correctly and the retaining screws fitted before
re-connecting the electrical supply.
Before service or maintenance work, disconnect the Aquapoint
from the power supply network
This must only be performed by a trained professional
!
!
Fig. 5 Removing the protective cover
!
!