Exhaust air fan Aero_aH 100 with integrated room and cellar dehumidification control
1019-1-0002
Handbuch 31.01.2021_JUSC_Aero_aH100|
21
2.
Insert the supplied indoor climate sensor
[5] correctly (
→
arrow X) in the
connection socket.
3.
Attach the cover [4].
Please note that the membrane
located on the flat side of the sensor
housing must not be exposed to
mechanical stress.
7.6.
Commissioning
1.
Switch on the mains fuse.
2.
Run a function test.
3.
Save the reference humidity by pressing
button 1 [15].
4.
Fit the design cover [3].
Saving of the reference values is
shown by LED 1 blinking.
8.
Maintenance
The unit is maintenance-free.
9.
Cleaning
DANGER
Danger to life from electric
shock
Switch off the mains fuse
.
ATTENTION
: Risk of damage
to the unit if the wrong
cleaning agent is used.
Clean cover [4] and design
cover [3] with water only. Do
not use aggressive cleaning
agents.
1.
Clean the inner parts of the fan with a dry
cloth only.
2.
If the design cover [3] is very dirty, carefully
remove it and clean it with water.
3.
Reinstall the design cover [3].
10.
Troubleshooting
•
In the event of any malfunction, consult a
qualified electrician.
•
Repairs may only be carried out by
qualified electricians.
DANGER
Danger to life from electric
shock
Switch off the mains fuse
before working on electrical
connection
Both LEDs off No mains voltage
Check whether the mains
fuse has failed. Switch it on,
if necessary.
Both LEDs
light up
three
times
Error indoor climate sensor.
The indoor climate sensor
could not be found. Check
that it is firmly attached and
that it is correctly positioned.
Both LEDs
light up
five
times
Error outdoor climate sensor
The connection to the
outdoor climate sensor has
been interrupted. Check
sensor connection cable and
connector contact.