Operating instructions type-lines CXE/AVC (E)
Date 0917
TBL02_13-GB 0917
Art.-Nr. 00153342-GB
Seite 46 / 63
13.2.1 Enable ON / OFF Funktion 1D
Remote ON / OFF (electronic disconnection) contact free of potential, operation of the device is still possible after
pressing the “ESC“ hotkey combination in switched-off condition. Signal- in and outputs remain active
A programmed operating indicator relay (factory set K1 function 1K) reports the switch-off.
A programmed alarm relay (factory set K2 function 2 K) does not report the switch-off.
No disconnection (isolation)) when turned off, in accordance with VBG4
§6.
Display STOP for swich off by remote switch at digital input e. g. Digital IN 1 = D1-D1
Controller ON for closed contact
D1 Inverting OFF D1-D1 bridged =controller ON
Controller ON with opened contakt
D1 Inverting ON
D1-D1 open = controller ON
13.2.2 External fault Function 2D
Connecting an external alarm indication (via floating contact).
The device continues to work unchanged during an external indication to the digital input; the alarm symbol appears in
the display. This indication can be issued via the relay contacts (K1, K2) (
)
IO Setup function K1, K2).
Indication during closed contact (factory preset)
D1 Inverting OFF
Indication during opened
contact D1
Inverting
ON