Operating instructions type-lines CXE/AVC (E)
Date 0917
TBL02_13-GB 0917
Art.-Nr. 00153342-GB
Seite 38 / 63
10. Menu group Start
11. Menu group Info
For mode speed controller
1.01
Modulation of the controller device in
addition to the bar display.
Display of the type and level of the active
default signal in percent
(0-100 % ^ 0-10 V, 10-0 V, 0-20 mA, 20-0
mA, 4-20 mA, 20-4 mA).
Display:
the device operates at :
Set „External 1“ = Signal to „E1“ / „GND“
Set „External 2“ = Signal to „E2“ / „GND“
Set „Intern 1“ = Menu „Set intern 1“
Set „Intern 2“ = Menu „Set intern 2“
Info for mode controller
2.01
..,,
3.01
..,,
4.01
..,
5.01
..,
6.01
..,
Current actual value measured on the
sensor 1. Depending sensor-type, in mbr,
m
3
/s, m/s, Pa, %, bar, m
3
/h, °C, V, mA,
etc.
For operation with two sensors display for
„E2 actual “. If function not active, display
- - - - -
Display of the active target value at which
the device operates
„Setpoint 1“ = Menu Setting
Setpoint 1
„Setpoint 2“ = Menu Setting
Setpoint 2
„Ext. Setpoint = setting by external signal
0-10 V. With activated manual mode the
display constantly changes between
actual value and value for ”manual
mode”.
Modulation of the controller device, in
addition to the bar display.
Momentarily status for minimum speed
cut off
Msco.“ : ON = switch off, if Setpoint (
±
Min. speed cut off) is reached
“Msco“ : OFF = no switch off that means
operation with minimum rate of air.
The service menu for the installation can be protected
against unintentional changes by a pin code.
With further pin codes putting back to pre-setting is
possible.
PIN 0010
Opening service menu, if PIN-protection activated
PIN 1234
opening “
setting
“, if “set protection“ ON (
)
Controller
Setup)
PIN 9090
Restore user setting
PIN 9091
Save user setting (corresponds function “Save user
setup ON”
)
Controller Setup)
PIN 9095
Restore factory setting = delivery status
Example for PIN input 0010 for
opening service menu
Menu language
by the factory set to
English.
In this menu different national languages
can be selected (GB = English, D =
Deutsch ...).
Complete re-start of the device.
Query of the operating mode
Query of the device software version
Announcement of the currnet time
Announcement of the currnet date