Operating instructions type-lines CXE/AVC (E)
Date 0917
TBL02_13-GB 0917
Art.-Nr. 00153342-GB
Seite 32 / 63
↓
↑
↓
↑
↓
↑
↓
↑
↓
↑
↓
↑
↓
P
↑
ESC
9.5.2 Setting for operation modes
5.01
and
5.02
5.01
Volume control, Setpoint in m3/h (m3/s)
5.02
Volume control for ventilation systems setpoint
depending on outdoor temperature Setpoint in
Pa (hPa, mbar) and temperature in °C.
Setpoint 1
Setting range:
in measuring range of sensor and
“K” factor
Setpoint 2
Switch over 1/2 by external contact
(
)
IO Setup)
Control range „Pband“
small range = short control time
Big range = longer control times
(higher controller stability)
Minimal speed
0-100 %
Maximal speed
100% - Min.
OFF = automatic control
ON = manual speed setting 0 - 100
%
Manual speed setting
0 - 100 % if manual mode = ON
Additional menu item for mode
5.02
with outside-
temperature dependent target-setpoint
An outside temperature compensation can be activated
(sensor connection E2 to analog IN 2) when being
operated as a pressure regulation device. An optimal
building climate, e.g., can be achieved through this.
Through this function, the set and active Setpoint1/2 is
automatically changed proportional to the measured
outside temperature (
)
Info: “Setpoint control“).
Temperature range in which the
setpoint change continiously with
outside temperature
Setpoint reducing will start below
this outside temperature (start
point)
Minimum air volume for very low
outside temperature
↓
↑
↓
↑