Operating instructions type-lines CXE/AVC (E)
Date 0917
TBL02_13-GB 0917
Art.-Nr. 00153342-GB
Seite 15 / 63
↓
P
↑
ESC
↓
↑
↓
↑
9.2 Temperature control
2.01
..
2.05
9.2.1 Basic setting
2.01
..
2.05
In all group 2 operating modes
(
2.01
,
2.02
,
2.03
, ....)
E1 analogue input IN factory set
to „
TF
“
Alternative selection signal: 0-10 V, 0-20 mA, 4-20 mA,
jumper accordingly inserted. The sensor
measurement-range must be entered in order to
correctly display the actual value. Example with a 0-10
V sensor and 0-100° C measurement range
Initial value measuring range
Final value measuring range
Decimal places
display unit
Sensor calibration with calibrated
comparison device
Function analog Input 2
•
External setpoint = Function 1E
by external signal (0-10 V) instead of
„Set point 1“
For sensor type „E1 TF“..: 0-10 V ^ -27°C..+75.0°C
For sensors with active signal:
0-10 V ^ 0-100 % sensor measuring range
•
External manual operation via external signal (0-10V) =
function 2E
Switch over between settings on the device and external
manual operation via digital input (
)
IO Setup).
•
Measurement value = function 7E
e.g. for limit indication, display in Info menu “E2 actual”
•
Modes with two sensors
The function is automatically jointly programmed in operating
modes using 2 sensors. The second analog input is thus
allocated and additional function allocations are not possible.
2.04
E2 Function at 4E preprogrammed = comparison value with
control to higher temperature.
alternative: average of 2 measuring points for this must be
reprogrammed on function 3E preprogrammed sensor type
TF..
2.05
E2 Function at 5E preprogrammed = regulation on
difference temperature between sensor 1 and sensor 2.
Preprogrammed sensor type TF..