9.5 Volume control
5.01
,
5.02
9.5.1 Basic setting
5.01
,
5.02
For all modes in group 5 (
5.01
and
5.02
....)
Analog In E1 factory setting to DSG200
Selection sensor measuring range: DSG 50, *DSG100
DSG200, *DSG300 DSG500, DSG1000, DSG2000,
DSG4000, DSG6000
(* no Ziehl-Abegg standard type)
For sensors with 0-20 mA, 4-20 mA signal put Jumper
accordingly and select measuring range DSG50 ..
DSG6000.
Input of the K of factor dependent on
the fan (inlet duct)
setting range 0..7.000
Sensor calibration with calibrated
comparison device
Function Analog Input 2
•
External setpoint = Function 1E by external signal
(0-10 V) instead of „Setpoint 1“
0-10 V ^ 0-100 % setting range
•
External manual operation via external signal (0-10V)
= function 2E
Switch over between settings on the device and
external manual operation via digital input
(
)
IO Setup).
•
Measurement value = function 7E
e.g. for limit indication, display in Info menu “E2 actual”
•
Modes with two sensors
The function is automatically jointly programmed in
operating modes using 2 sensors. The second analog
input is thus allocated and additional function
allocations are not possible.
5.02
E2 Function at 6E preprogrammed = sensor for setpoint
lowering. Pre-programmed sensor type TF....