Query data / received reply
Frame
Byte
Value
Description
Remarks
7
0002
Option value (Lo)
8
0x00
Data value (Hi)
Data value
9
0x01
Data value (Lo)
Query data / received reply
Frame
Byte
Value
Description
Remarks
Head
0
0x12
(query)
0x22
(reply)
Meter
Runs automatically continuously from
0x01...0xFF, e.g. 0x12 and 0x22
1
0x08
Length
Always for function 103
MODBUS
2
0x02
Device address
(MODBUS)
Address the devices in order
3
0x67
Command
0x67 (=103) ZIEHL-ABEGG user func-
tion
4
0x00
Sub-function (Hi)
0x0040 = auto-addressing
5
0x40
Sub-function (Lo)
6
0x00
Option value (Hi)
Phase 2
7
0002
Option value (Lo)
8
0x00
Data value (Hi)
Data value
9
0x02
Data value (Lo)
Query data / received reply
Frame
Byte
Value
Description
Remarks
Head
0
0x13
(query)
0x23
(reply)
Meter
Runs automatically continuously from
0x01...0xFF, e.g. 0x13 and 0x23
1
0x08
Length
Always for function 103
MODBUS
2
0x03
Device address
(MODBUS)
Address the devices in order
3
0x67
Command
0x67 (=103) ZIEHL-ABEGG user func-
tion
4
0x00
Sub-function (Hi)
0x0040 = auto-addressing
5
0x40
Sub-function (Lo)
6
0x00
Option value (Hi)
Phase 2
7
0002
Option value (Lo)
8
0x00
Data value (Hi)
Data value
9
0x03
Data value (Lo)
Operating Instructions
NETcon
D-G-64NE
Communication
L-BAL-E273-GB 1631 Index 001
Part.-No.
22/27