6.4 Read data
Read Holding Register (3) / Read Input Register (4)
Request data
Frame
Byte
Value
Description
Remarks
Head
0
0x18
Meter
Runs automatically continuously from
0x01...0xFF, e.g. 0x18
1
0x06
Length
"6" for reading data
MODBUS
2
0xF7
Address
Always 247
3
0x03
Command
3 means reading
4
0x00
Register Index (Hi)
Register index (possible: 0 to 49), e.g.
H2
5
0x02
Register Index (Lo)
6
0x00
Register data (Hi)
Counts the queried data (1 to 2)
7
0x01
Register data (Lo)
8
0x00
do not use
9
0x00
do not use
Received reply
Frame
Byte
Value
Description
Remarks
Head
0
0x18
Meter
Runs automatically continuously from
0x01...0xFF, e.g. 0x18
1
0x05
Length
"5" for reading data
MODBUS
2
0xF7
Address
Always 247
3
0x03
Command
3 means reading
4
0x02
Data meter
Data meter (number of bytes received)
5
0x00
Register data (Hi)
Here: 2 data bytes received, e.g. 0xC8
(=200)
6
0xC8
Register data (Lo)
7
0x00
do not use
8
0x00
do not use
9
0x00
do not use