![ZIEHL-ABEGG Icontrol FXDM Series Operating Instructions Manual Download Page 88](http://html1.mh-extra.com/html/ziehl-abegg/icontrol-fxdm-series/icontrol-fxdm-series_operating-instructions-manual_3733913088.webp)
14
Enclosure
14.1
Technical data
The name plate data for the rated current* output refer to a maximum ambient temperature of 40
°
C.
For higher temperatures note following position for operation with higher ambient temperature.
Type
(Part-No.)
Rated cur-
rent*
Output
{1}
[A]
Rated cur-
rent
(
I
funda-
mental com-
ponent @
50 Hz)
Input
{1}
[A]
Recom-
mended
motor out-
put
{2}
[kW]
max. line
fuse
{3}
[A]
max. heat
dissipation
{1}
[W]
Noise ap-
prox.
{4}
[dB]
Weight
[kg]
Housing
protection
IP
FXDM2.6A
(308063)
2.6
2,6 (2,4)
1.1
6
45
-
3.2
54
FXDM2.6AQ
(308161)
2.6
2,6 (2,4)
1.1
6
45
-
3.4
54
FXDM4.2A
(308148)
4.2
3,9 (3,5)
1.5
10
70
-
6.4
54
FXDM4.2AQ
(308162)
4.2
3,9 (3,5)
1.5
10
70
-
6.6
54
FXDM5A
(308149)
5.0
4.8 (4.4)
2.2
10
80
-
6.4
54
FXDM5AQ
(308163)
5.0
4.8 (4.4)
2.2
10
80
-
6.6
54
FXDM7.5A
(308150)
7.5
6,5 (6,1)
3.0
10
125
-
7.3
54
FXDM7.5AQ
(308164)
7.5
6,5 (6,1)
3.0
10
125
-
7.5
54
FXDM8.5A
(308151)
8.5
7,8 (7,3)
4.0
10
150
-
7.3
54
FXDM8.5AQ
(308165)
8.5
7,8 (7,3)
4.0
10
150
-
7.5
54
FXDM12A
(308152)
12
10,9 (9,9)
5.5
16
210
-
7.5
54
FXDM12AQ
(308166)
12
10,9 (9,9)
5.5
16
210
-
7.7
54
FXDM17A
(308153)
17
15,4 (14,1)
7.5
20
300
-
7.5
54
FXDM17AQ
(308167)
17
15,4 (14,1)
7.5
20
300
-
7.7
54
FXDM25A
(308112)
25
25 (-)
11.0
35
480
-
12.5
54
FXDM25AQ
(308168)
25
25 (-)
11.0
35
480
-
12.8
54
FXDM32A
(308078)
32
27.6 (25.7)
15.0
35
750
65.7
24.5
54
FXDM32AQ
(308169)
32
27.6 (25.7)
15.0
35
750
65.7
25,3
54
FXDM32AE
(308079)
32
27.6 (25.7)
15.0
35
750
65.7
24.2
20
FXDM39A
(308080)
39
34.0 (31.5)
18.5
50
900
65.7
26.3
54
FXDM39AQ
(308170)
39
34.0 (31.5)
18.5
50
900
65.7
27.1
54
Operating Instructions
Icontrol
–
model series FXDM
Enclosure
L-BAL-E036-GB 1422 Index 008
Part.-No. 00154773-GB
88/96