![ZIEHL-ABEGG Icontrol FXDM Series Operating Instructions Manual Download Page 23](http://html1.mh-extra.com/html/ziehl-abegg/icontrol-fxdm-series/icontrol-fxdm-series_operating-instructions-manual_3733913023.webp)
8
Start-up
8.1
Prerequisites for commissioning
Attention!
1. You must mount and connect the device in accordance with the operating instructions.
2. Double check that all connections are correct.
3. The mains voltage must match the information on the rating plate.
4. The rated current on the rating plate will not be exceeded.
5. Make sure that no persons or objects are in the fan's hazardous area.
8.2
Procedure for commissioning
Sequence
Setting
1
Check if Thermostats or Thermistors of the motor are connected to input
“
TB/TP In
”
.
If the motor protection function of the device is not neccesary the both terminals
“
TB / TP
”
have to be bridged.
2
Check connection and close housing carefully.
3
Turn on mains voltage.
Display after
fi
rst turning on the mains voltage.
4
In menu group
Start
the adjustment for
Motor
is
“
OFF
”
for factory setting.
This prevents the system from inadvertently starting up before con
fi
guration is complete.
Operation of the device after pressing the
“
Esc
”
hotkey combination.
Settings for U/f characteristic can only be made when no motor modulation is present! This is the same also for
the setting of Mode.
Switch-over between
“
OFF
”
and
“
Start
”
with the key shortcut for Es-
cape ((Esc =
▼
+
▲
).
5
If necessary, set the menu language in Menu group
Start
.
(Factory setting Englisch:
“
Language GB
”
)
4
Set the operating mode in the
Base setup
menu group (factory settings
1.01
=
speed controllers
).
Attention!
When saving the operating mode, the respective preset factory operating-mode setting is loaded. That means,
the settings you have made, e.g., in
“
Motor setup
”
are lost. An exception: the menu language setting remains
preserved.
5
The settings in the
Motor setup
depend on the type of motor connected.
5.1
: Setting motor rated current
5.2
: Setting motor rated voltage
5.3
: Setting Edgefrequency
5.4
: Setting maximum frequency
Additional settings as required
Motor setup
6
In menu group
Start
switch setting for
Motor
to
“
ON
”
.
Additional setings (
Programming and selected Mode).
Operating Instructions
Icontrol
–
model series FXDM
Start-up
L-BAL-E036-GB 1422 Index 008
Part.-No. 00154773-GB
23/96