Setpoint1
Setpoint1
3.01
and
3.03
Setting range: in measuring range of sensor, factory setting: 12.0 bar
3.02
and
3.04
Setting range: dependent on the selected refrigerant, factory setting:
35.0
°
C
Setpoint1
Setpoint2
Setpoint2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (as long as no allocation is carried out:
Display:
|
- - - - -
|
IO Setup).
Pband
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
3.01
and
3.03
Setting range: in measuring range of sensor, factory setting: 5.0 bar
3.02
and
3.04
Setting range: dependent on the selected refrigerant and in measuring
range of sensor, factory setting: 7.0 K
Pband
Min. Speed
Min. Speed
(basic speed only when needed)
Setting range:
|
OFF
|
→
“
Shutdown Freq.
”
(
Motor Setup) -
“
Max. Speed
”
.
Factory setting:
|
OFF
|
Max. Speed
Max. Speed
(speed limitation only when needed)
Setting range:
“
Max. Frequency
”
(
Motor Setup) -
“
Min. Speed
”
Factory setting: 50.0 Hz
Manual mode
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
Speed man.
Speed Manual mode
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
IO Setup).
Setting range: 0...
“
Max. Frequency
”
(
Motor Setup)
Factory setting: 50.0 Hz
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
Operating Instructions
Icontrol
–
model series FXDM
Programming
L-BAL-E036-GB 1422 Index 008
Part.-No. 00154773-GB
35/96