![ZIEHL-ABEGG Icontrol FXDM Series Operating Instructions Manual Download Page 40](http://html1.mh-extra.com/html/ziehl-abegg/icontrol-fxdm-series/icontrol-fxdm-series_operating-instructions-manual_3733913040.webp)
E1 Offset
E1 Offset
Sensor calibration with calibrated comparison device
E2 Function
E2 Function
(only for special applications)
•
External setpoint = Function
|
1E
|
by external signal (0 - 10 V) instead of
“
Setpoint 1
”
. 0 - 10 V
0 - 100 % setting range
•
External manual operation via external signal (0 - 10 V) = Function
|
2E
|
Switch
over between settings on the device and external manual operation via digital
input (
IO Setup).
•
Measurement value = function
|
7E
|
e.g. for limit indication, display in Info menu
“
E2 Actual
”
Modes
5.02
with two sensors
Modes with two sensors The function is automatically jointly programmed in operating
modes using 2 sensors. The second analog input is thus allocated and additional
function allocations are not possible. For
5.02
E2 Function at
|
6E
|
preprogrammed =
sensor for setpoint lowering. Pre-programmed sensor type
“
TF
”
.
9.5.2
Setting for operation modes
5.01
...
5.02
•
5.01
Volume control, Setpoint in m
3
/h
•
5.02
Volume control for ventilation systems setpoint depending on outdoor temperature.
Setting
Setting
Setpoint1
Setpoint1
Setpoint in m
3
/h (m
3
/s)
Setting range: depending on measuring range of sensor and
“
K factor
”
Factory setting: 530 m
3
/h
Setpoint2
Setpoint2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (as long as no allocation is carried out:
Display:
|
- - - - -
|
IO Setup).
Pband
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Setting range: depending on measuring range of sensor and
“
K factor
”
Factory setting: 530 m
3
/h
Min. Speed
Min. Speed
(basic speed only when needed)
Setting range:
|
OFF
|
→
“
Shutdown Freq.
”
(
Motor Setup) -
“
Max. Speed
”
.
Factory setting:
|
OFF
|
Max. Speed
Max. Speed
(speed limitation only when needed)
Setting range:
“
Max. Frequency
”
(
Motor Setup) -
“
Min. Speed
”
Factory setting: 50.0 Hz
Manual mode
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
Speed man.
Speed Manual mode
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
IO Setup).
Setting range: 0...
“
Max. Frequency
”
(
Motor Setup)
Factory setting: 50.0 Hz
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
Operating Instructions
Icontrol
–
model series FXDM
Programming
L-BAL-E036-GB 1422 Index 008
Part.-No. 00154773-GB
40/96