9.9.7.2
Control group 2/3/4 via relais
Group 2 ON value
Group 2 ON value
Switch-on value for Group2
Setting range: 0 - 100 %
Factory setting: 50 % *
OFF Value Group2
OFF Value Group2
Switch-off value for group2
Setting range: 0 - 100 %
Factory setting: 45 % *
nmin at Group2
nmin at Group2
Minimum Value for Group2
Setting range: 0 - 100 %
Factory setting: 20 % *
When more than two groups add-on module necessary
type Z-Modul-B (Part.-No. 380052).
Group 3 ON value
Group 3 ON value
Switch-on value for Group3
Setting range: 0 - 100 %
Factory setting: 70 % *
OFF Value Group3
OFF Value Group3
Switch-off value for group3
Setting range: 0 - 100 %
Factory setting: 65 *
nmin at Group3
nmin at Group3
Minimum Value for Group3
Setting range: 0 - 100 %
Factory setting: 30 % *
Group 4 ON value
Group 4 ON value
Switch-on value for Group4
Setting range: 0 - 100 %
Factory setting: 85 % *
OFF Value Group4
OFF Value Group4
Switch-off value for group4
Setting range: 0 - 100 %
Factory setting: 80 % *
nmin at Group4
nmin at Group4
Minimum Value for Group4
Setting range: 0 - 100 %
Factory setting: 40 % *
*
As long as in IO Setup
“
K Function
”
not programmed display:
|
- - - -
|
Higher settings must be chosen for subsequent groups. Switch-off value of the group always below
the switch-on value.
Function
•
Group 1 continuously controlled by the device
’
s
“
Master
”
power unit (
motor connection).
•
Other motors are switched directly to line voltage by contactors via the relay outputs
“
K1..K4
”
.
Depending on the additional groups count the function for the relays must be programmed (IO
Setup / K.. Function:
|
8K
|
= group 2,
|
12K
|
= group 3,
|
13K
|
= group 4). Keep the order!