2 x relay outputs (
“
K3
”
and
“
K4
”
) Function programmable, e.g., for: Status signals, alarm
indications, external malfunctions at the digital input, level-control threshold, input signal thresh-
old, offset threshold (deviation between current and target value), group control.
Parameter
Factory setting
User Setting
Z-Modul-B
42
44
41
32
34
31
A2 GND E3 GND D3
D4
D5 GND
Ausgang
0...10V
(I
max
=10mA)
+
Eingang
0...10V
(Ri>100k)
+
max. Kontaktbelastung 5A/250VAC
A
n
a
lo
g
O
U
T
2
3
2
A
n
al
o
g
I
N
3
D
ig
it
a
l
IN
3
D
ig
it
a
l
IN
4
D
ig
it
a
l
IN
5
K4
K3
04.04.2007
v_moea01k0.VSD
Programming of following functions of mode
2.03
is not
permissible on Z-Modul-B:
|
6A
|
,
|
7A
|
,
|
9K
|
,
|
10K
|
A2 Function
1A
A2 min.
0.0 V
A2 max.
10.0 V
A2 Inverting
OFF
D3 Function
OFF
D3 Inverting
- - - -
D4 Function
OFF
D4 Inverting
- - - -
D5 Function
OFF
D5 Inverting
- - - -
E3 Function
OFF
E3 Inverting
- - - -
K3 Function
OFF
K3 Inverting
- - - -
K4 Function
OFF
K4 Inverting
- - - -
9.10.6
Networking via MODBUS
It is possible to network several devices with each other. The device uses the MODBUS-RTU as the
protocol for the RS-485 interface.
Bus Address
Bus Address
The device address (Device-ID) is factory set to the highest available MODBUS
address: 247
Thisaddressis reserved for operation with an external terminal and should not be
occupied with anything else.
Addressing
Addressing
Switch addressing to
“
ON
”
before setting
“
address
”
.
Reading and writing parameters
The device supports reading and writing processes for MODBUS Holding Registers. The start address
is
0
; the number of registers depends on the device. If the allowable start address or number is
exceeded, the device answers with an exception code. The description of the register is device
dependent and can be requested from service for the device/version concerned.