13
Enclosure
13.1
Technical data
The name plate data for the rated current* output refer to a maximum ambient temperature of 40
°
C.
For higher temperatures note following position for operation with higher ambient temperature.
Type
Part.-N-
o.
Rated cur-
rent*
Output
{1}
Rated cur-
rent
(
I
funda-
mental com-
ponent @ 50
Hz)
Input
{1}
max. line
fuse
{2}
Max. heat
dissipation
approx.
{1}
Noise ap-
prox.
{3}
Weight
Housing
protection
[A]
[A]
[A]
[W]
[dB]
[kg]
IP
FKDM5AM-C
308145
5
4.8 (4.4)
10
100
54.6
7.2
54
FKDM8AM-C
308146
8
7 (6.5)
10
150
54.6
7.9
54
FKDM12AM-C
308147
12
11.2 (10.4)
16
270
-
8.7
54
FKDM18AM-C
308122
18
16.3 (15.0)
20
440
-
14.2
54
FKDM22AM-C**
308199
22
19.2 (17.7)
25
520
-
14.5
54
FKDM32AM-C
308124
32
27.6 (25.7)
35
700
65.7
29.6
54
FKDM32AME-C
308125
32
27.6 (25.7)
35
700
65.7
33.1
20
FKDM40AM-C
308179
40
34.0 (31.5)
50
790
65.7
29.6
54
FKDM40AME-C
308180
40
34.0 (31.5)
50
790
65.7
33.1
20
FKDM50AM-C**
308185
50
47.5 (43.2)
63
910
65.7
32.8
54
FKDM50AME-C**
308186
50
47.5 (43.2)
63
910
65.7
36.7
20
A maximum starting current of times 2 of the rated frequency inverter current is possible!
{1}
At line voltage 400 V / 50 Hz (cos
φ
0.8 Output), data for deviating line voltages on request
{2}
Max. supply side line fuse according to DIN EN 60204-1 classi
fi
cation VDE0113 chapter 1
{3}
Sound power level A-weighted by internal fan (- no indication)
**)
For FKDM22 and FKDM50 rated current (output) only possible for motors wih cos
φ
< 0.8
Line voltage*
3 ~ 208...480 V (-15 up to +10 %), 50/60 Hz
Maximal output voltage
95 % of U
Line
Maximal output frequency
150 Hz
(for FKDM22 and FKDM50 up to 400 V line voltage max. 75 Hz, up to 480 V line
voltage max. 60 Hz permissible)
Power factor
> 0.9
Switching Freq.
16 kHz
Input resistance for sensor or signal
set for the rotational speed
for 0 - 10 V input: R
i
> 100 k
Ω
for 4 - 20 mA input: R
i
= 100
Ω
Voltage supply e.g. for sensors
+24 V
±
20 %, I
max
120 mA (for connection to an external AXG terminal minus approx.
50 mA)
Output (0 - 10 V)
I
max
10 mA (short-circuit-proof)
Max. contact rating of the internal relay 2 A / 250 VAC
Max. permissible ambient temperature 40
°
C (up to 55
°
C with derating)
Min. permissible ambient temperature 0
°
C (if mains voltage is not switched off up to -20
°
C)
Permissible temperature range for
storage and transport
-30...+80
°
C (FKDM22 and FKDM50: -30... +70
°
C)
Max. permissible installation height
0..4000 m amsl
above 1000 m amsl the rated current is to be reduced by 5 % / 1000 m
Permissible rel. humidity
85 % no condensation
Electromagnetic compatibility for the
standard voltage 230 / 400 V accord-
ing to DIN IEC 60038
Interference emission EN 61000-6-3 (domestic household applications)
By special version for IT-System according to EN 61000-6-4 (industrial applications)
Interference immunity EN 61000-6-2 (industrial applications)
Operating Instructions
Fcontrol
–
model series FKDM..-C
Enclosure
L-BAL-E057-GB 1304 Index 009
Part.-No. 00163327-GB
68/74