Parameter
Factory setting
User
Setting
0
Setting
Setpoint1
1.00 bar
1.00 bar
- 10.0
°
C
- 10.0
°
C
Setpoint2
- - - -
- - - -
- - - -
- - - -
Pband
3.00 bar
3.00 bar
5.0 K
5.0 K
Min. Speed
25.0 Hz
30.0 Hz
25.0 Hz
30.0 Hz
Max. Speed
50.0 Hz
87.0 Hz
50.0 Hz
87.0 Hz
Manual mode
OFF
OFF
OFF
OFF
Speed man.
50.0 Hz
50.0 Hz
50.0 Hz
50.0 Hz
Events
Base setup
Mode
3.10
3.11
3.20
3.21
3.10
Suction-pressure control, maximum
output frequency 50 Hz
3.11
Suction-pressure control, maximum
output frequency 87 Hz
3.20
Back pressure regulation with input
for refrigerant, maximum output frequency
50 Hz
3.21
Back pressure regulation with input
for refrigerant, maximum output frequency
87 Hz
E2 Function
|
1E
|
external Setpoint
|
2E
|
external Manual mode
|
3E
|
Sensor average to E1
|
4E
|
Sensor comparison to E1
|
5E
|
Sensor difference to E1
|
6E
|
Sensor for Setpoint
|
7E
|
Measurement value
E1 Analog In
-1 - 7 MBG
-1 - 7 MBG
-1 - 7 MBG
-1 - 7 MBG
E1 Refrigerant
R407C
R407C
E1 Min.
- - - -
- - - -
- - - - -
- - - -
E1 Max.
- - - -
- - - -
- - - - -
- - - -
E1 Decimals
- - - -
- - - -
- - - - -
- - - -
E1 Unit
- - - -
- - - -
- - - - -
- - - -
E1 Offset
0.0 bar
0.0 bar
0.0 K
0.0 K
E2 Function
2E
2E
2E
2E
E2 Analog In
0 - 10 V
0 - 10 V
0 - 10 V
0 - 10 V
E2 Min.
0.0 V
0.0 V
0.0 V
0.0 V
E2 Max.
10.0 V
10.0 V
10.0 V
10.0 V
E2 Decimals
1
1
1
1
E2 Unit
V
V
V
V
E2 Offset
0.0 V
0.0 V
- - - -
0.0 V
0.0 V
Controller Setup
PIN Protection
OFF
OFF
OFF
OFF
Set protection
OFF
OFF
OFF
OFF
Save User Setup
OFF
OFF
OFF
OFF
Alarm sensors
OFF
OFF
OFF
OFF
Limit
- - - - -
- - - - -
- - - - -
- - - - -
Min. speed cut off
OFF
OFF
OFF
OFF
Group 2 ON value
- - - - -
- - - - -
- - - - -
- - - - -
OFF Value Group2
- - - - -
- - - - -
- - - - -
- - - - -
nmin at Group2
- - - - -
- - - - -
- - - - -
- - - - -
Group 3 ON value
- - - - -
- - - - -
- - - - -
- - - - -
OFF Value Group3
- - - - -
- - - - -
- - - - -
- - - - -
nmin at Group3
- - - - -
- - - - -
- - - - -
- - - - -
Group 4 ON value
- - - - -
- - - - -
- - - - -
- - - - -
OFF Value Group4
- - - - -
- - - - -
- - - - -
- - - - -
nmin at Group4
- - - - -
- - - - -
- - - - -
- - - - -
Val > Set=n+
ON
ON
ON
ON
Type of control
P
P
P
P
KP
50 %
50 %
50 %
50 %
Operating Instructions
Fcontrol
–
model series FKDM..-C
Programming
L-BAL-E057-GB 1304 Index 009