Function
Description
OFF
No function
Relays remain always de-energized
1K
Operating indication (factory setting for
“
K1
”
, non inverting).
Operation without fault, reports enable
“
OFF
”
2K
Fault indication (factory setting for
“
K2
”
, non inverting).
Energized for operation without fault, for enable
“
OFF
”
not energized. De-energized at line,
motor and controller fault, Sensor fault dependent on programming, external fault at digital
input.
3K
External fault separate with message at digital input (factory setting if terminals bridged)
4K
Limit modulation
Over or falling below limits for modulation
5K
Limit
“
E1
”
When over or falling below limits for input signal
“
E1
”
6K
Limit
“
E2
”
When over or falling below limits for input signal
“
E2
”
8K
Group control (Group 2)
Switching on motors depending on modulation
12K *
Group control (Group 3)
Switching on motors depending on modulation
13K *
Group control (Group 4)
Switching on motors depending on modulation
For modes as controller higher
3.10
7K
Setpoint Offset
Deviation between actual value and setpoint to high
12
14
11
22
24
21
K1
K2
11.05.2007
v_relais_k1_k2.vsd
K1
1
= energized, terminals 11-14 bridged
0
= de-energized, terminals 11-12 bridged
K2
1
= energized, terminals 21-24 bridged
0
= de-energized, terminals 21-22 bridged
Function Controller status
K1/ K2
1 = energized
0 = de-energized
Inverting
OFF
ON
1K
Operation without fault, line supply okay
1
0
2K
Fault with indication by relay
0
1
3K
Ext. Fault at digital input for external fault
1
0
4K
Over or falling below limits for modulation
1
0
5K
over or falling below limits for input signal
“
E1
”
1
0
6K
over or falling below limits for input signal
“
E2
”
1
0
7K
setpoint deviation to high
1
0
8K
Activation of second group
1
0
12K
Activation of third group
1
0
13K
Activation of fourth group
1
0
9.6.5
Programming Add-on module type Z-Modul-B
Program the additional inputs and outputs likewise in
“
IO Setup
”
.
After connecting the module, the settings menus are automatically expanded to include the additional
inputs and outputs.
•
1 x analog input 0 - 10 V. For mode
1.10
...
1.11
without function, starting from
3.10
funktion
|
1E
|
or
|
2E
|
possible.
–
Function
|
1E
|
for external target value function.
–
Function
|
2E
|
for external manual operation.
Operating Instructions
Fcontrol
–
model series FKDM..-C
Programming
L-BAL-E057-GB 1304 Index 009
Part.-No. 00163327-GB