9.6.2.8
Automatic control / speed manual Function
|
7D
|
(mode
3.10
)
Factory setting for digital input
“
D2
”
.
Switch over between automatic control to set target value (depending on the activation:
“
Setpoint1
”
,
“
Setpoint2
”
) and the default for
“
manual operation
”
set at the device.
If for input 2
“
E2 Function
”
the function is programmed to
|
2E
|
switch over between
“
Setpoint 1
”
or
“
Setpoint 2
”
and external Manual mode.
With activated manual mode the value
“
Set external2
”
is displayed in menu group
“
Info
”
.
Contact at digital input e.g.
“
Digital In 1
”
Controller
D1 D1
1
0
n = 0 -100 %
1
n = 80 %
0
- - - - -
- - - - -
- - - - -
Se
E1
ES
E2
27.11.2008
v_7d_regelung_hand_m.vsd
3
2
1
M
1
Setting
“
Setpoint1
”
2
Setting
“
Setpoint2
”
3
Setting
“
Speed manual
”
EH
Signal for Manual mode extern, E2 Function =
|
2E
|
Se
Sensor
•
“
D1 Inverting
”
=
“
OFF
”
Automatic
control at opened contact / manual
operation at closed contact.
•
“
D1 Inverting
”
=
“
ON
”
: Automatic control
at closed contact / manual operation at
opened contact.
9.6.2.9
Reverse action of control function (
3.10
), Function
|
8D
|
Switchover between: Increasing modulation during increasing actual-value and increasing modulation
during sinking actual-value.
The factory presets for the
“
Control function
”
are dependent on the selected mode of operation (
Controller Setup - reverse operation of the control function).
When switching over via a digital input, the device works with the opposite function than the one set
there!
Val>Set=n+
Settings in Controller Setup
9.6.2.10
Reset, Function
|
10D
|
Reset after motor fault by using an non-locking reset key. The unit switches off when interruption
between both
“
TB/TP
”
or
“
TK/PTC
”
terminals, the unit then remains switched off (
“
motor fault
”
see
motor protection). Re-starting after the drive has cooled down (terminals
“
TB/TP
”
- or
“
TK/PTC
”
bridged) by non-locking reset key possible.
M
27.11.2008
v_10d_reset_m.vsd
Controller
D1 D1
Reset
TB/TP
Contact at digital input e.g.
“
Digital In 1
”
•
For
“
D1 Inverting
”
=
“
OFF
”
both
terminals
“
D1
”
-
“
D1
”
in normal operation
interrupted. Reset after fault by short
close.(For
“
Inverting
”
=
“
ON
”
reverse
function).
Operating Instructions
Fcontrol
–
model series FKDM..-C
Programming
L-BAL-E057-GB 1304 Index 009
Part.-No. 00163327-GB
48/74